—P100 Series Encapsulated Pressure Controls Product/Technical Bulletin
Table 1: Standard P100 Control Models
Setting—psig (kPa) Replaces:
Product
Code
Number
Switch
Action
Application
Opens Closes Gemline Ranco
Robert-
shaw
Saginomiya
P100AP-201C
10 (69) 32 (221) - MPL-7011 3100-050 -
P100AP-2C
Low Cutout
35 (241) 60 (414) - MPL-7004 3100-004 -
P100AP-3C
150 (1034) 225 (1551) - MPF-7008 - ABC-AA01
P100AP-4C
Fan Cycling
170 (1172) 250 (1724) - - - -
P100AC-1C*
5 (34) 20 (138) - MPL-7001 - -
P100AC-2C*
Open on
Pressure
Drop
Low Cutout
15 (103) 30 (207) - MPL-7002 - -
P100CP-1C
400 (2758) 300 (2068) PC151 MPH-7107 3100-151 -
P100CP-2C
425 (2930) 325 (2241) PC100 MPH-7108 3100-100 -
P100CC-9C*
High Cutout
275 (1896) 175 (1207) - - 3100-112 -
P100DA-1C
410 (2827)
Lockout
Manual Reset
PC103 - 3100-103 -
P100DA-2C
475 (3275)
Lockout
Manual Reset
- - 3100-106 -
P100DA-35C
350 (2413)
Lockout
Manual Reset
--- -
P100DC-3C†
Open on
Pressure
Rise
High Limit
375 (2586)
Lockout
Manual Reset
--- -
Note: Standard P100 models come with 1/4 in. SAE female flare fitting with integral Schrader valve depressor and 48 in.,
#18 AWG insulated, stranded-copper wire leads.
* Includes conduit clamp for 3/8 in. flexible metal conduit. (See Figure 1.)
† Includes conduit box with opening for 1/2 in. conduit connector. (See Figure 1.)
Table 2: P100 Pressure Control Model Selection Matrix
P100 Direct mount, encapsulated pressure switch
A SPST Open-low switch action, automatic reset
C SPST Open-high switch action, automatic reset
D SPST Open-high switch action, manual reset lockout
E SPDT, automatic reset
A Open construction (no conduit clamp or conduit box)
C Conduit clamp or conduit box
E Heavy duty electrical contacts (high current capacity) models
G High cycle life (250,000 cycles) models, open construction (no conduit clamp or conduit box)
J High cycle life (250,000 cycles) models, with conduit clamp or conduit box
L Standard-plus duty electrical contacts (medium current capacity), open construction (no conduit clamp or
conduit box)
M Standard-plus duty electrical contacts (medium current capacity), with conduit clamp or conduit box
P Open construction (no conduit clamp or conduit box), upgraded style
Note: Not all matrix combinations are available. To verify product availability and for quantity orders of non-standard items,
contact Johnson Controls/PENN Refrigeration Application Engineering at (414) 524-5535.