User Guide
P-5215 Product Bulletin 5
Installation
The P-5215 Differential Pressure
Transmitter is factory calibrated
in the vertical position; therefore,
the unit MUST BE MOUNTED
WITHIN 15 ANGULAR
DEGREES OF THE VERTICAL
POSITION as indicated in Fig. 4.
Note: It is recommended that
a level be used to obtain this
vertical position.
Refer to Table 3 for a list of
items required to perform
installation and commissioning.
In order to maintain factory
calibration, it is recommended
that the sensing line lengths do
not exceed the parameters listed
in Table 4.
Note: Since the P-5215 is a
temperature sensitive device,
it should only be installed in a
conditioned space.
Commissioning Procedure on Next page