M9220-xxx-3 Electric Spring Return Actuators (Continued)
Technical Specifications
M9220-xxx Electric Spring Return Actuators (Part 1 of 2)
Product Codes M9220-AGx-3 Models: Floating
M9220-Bxx-3 Models: On/Off
M9220-GGx-3 Models: Proportional
M9220-HGx-3 Models: Proportional Adjustable
Power Requirements AGx, HGx, GGx
Models
AC 24 V (19.2 to 30 V) at 50/60 Hz: Class 2, 15.5 VA Running,
7.7 VA Holding Position;
DC 24 V (21.6 to 26.4 V): Class 2, 6.7 W Running, 2.9 W Holding Position
BAx Models AC 120 V (AC 102 to 132 V) at 60 Hz: 0.25 A Running, 0.13 A Holding Position
BDx Models AC 230 V (AC 198 to 264 V) at 50/60 Hz: 0.15 A Running, 0.09 A Holding Position
BGx Models AC 24 V (19.2 to 30 V) at 50/60 Hz: Class 2, 24.6 VA Running,
7.7 VA Holding Position;
DC 24 V (21.6 to 26.4 V): Class 2, 17.6 W Running, 2.8 W Holding Position
Transformer Sizing Requirements AGx, HGx, GGx
Models
20 VA Minimum per Actuator
Bxx Models 25 VA Minimum per Actuator
Input Signal/Adjustments AGx Models DC 0 (2) to 10 V or 0 (4) to 20 mA with Field Furnished 500 ohm resistor;
Switch Selectable Direct or Reverse Action with Signal Increase
, 500 ms minimum pulse width
GGx Models Factory Set DC 0 to 10 V, CW Rotation with Signal Increase;
Selectable DC 0 (2) to 10 V or 0 (4) to 20 mA with Field Furnished 500 ohm, 0.25 W minimum
resistor; Switch Selectable Direct or Reverse Action with Signal Increase
HGx Models Factory Set DC 0 to 10 V, CW Rotation with Signal Increase;
Selectable DC 0 to 10 V or 0 to 20 mA with Field Furnished 500 ohm,
0.25 W minimum resistor;
Start Point Programmable DC 0 to 10 V;
Span Programmable DC 2 to 10 V;
Switch Selectable Direct or Reverse Action with Signal Increase
Control Input Impedance GGx, HGx Models Voltage Input: 200,000 ohms;
Current Input: 500 ohms with Field Furnished 500 ohm Resistor
Feedback Signal GGx Models 0 (2) to 10 VDC for Desired Rotation Range up to 90°;
Corresponds to Rotation Limits, 1 mA maximum
HGx Models 0 to 10 VDC for Desired Rotation Range up to 90°;
Corresponds to Rotation Limits, 1 mA maximum
Auxiliary Switch Rating xxC Models Two Single-Pole, Double-Throw (SPDT), Double-Insulated Switches with Gold Flash Contacts:
AC 24 V, 50 VA Pilot Duty;
AC 120 V, 5.8 A Resistive, 1/4 hp, 275 VA Pilot Duty;
AC 240 V, 5.0 A Resistive, 1/4 hp, 275 VA Pilot Duty
Spring Return Direction is Selectable with Mounting Position of Actuator:
Side A, Actuator Face Away from Damper for CCW Spring Return;
Side B, Actuator Face Away from Damper for CW Spring Return
Running and Spring Return Torque 177 lb·in (20 N·m) for a Single Actuator;
354 lb·in (40 N·m) for Two Models Mounted in Tandem
531 lb·in (60 N·m) for Three Models Mounted in Tandem
Valid Tandem Combinations Two M9220-Bxx-3
Three M9220-AGx-3
One M9220-HGx-3 master with one or two M9220-GGX-3 slaves
One M9220-GGx-3 master with one or two M9220-GGX-3 slaves
Rotation Range Adjustable from 30 to 90° CW or CCW with Optional
M9220-603 Adjustable Stop Kit; Mechanically Limited to 90°
Rotation Time
Power On (Running)
AGx, HGx, GGx
Models
150 Seconds for 0 to 177 lb·in (0 to 20 N·m) at All Operating Conditions; Independent of Load
BGx Models 24 to 57 Seconds for 0 to 177 lb·in (0 to 20 N·m) at All Operating Conditions; 35 Seconds
Nominal at Full Rated Load
Rotation Time
Power Off
(Spring Returning)
AGx, HGx, GGx
Models
20 Seconds for 0 to 177 lb·in (0 to 20 N·m) at Room Temperature
BGx Models 11 to 15 Seconds for 0 to 177 lb·in (0 to 20 N·m) at Room Temperature;
35 Seconds Maximum for 0 to 177 lb·in (0 to 20 N·m) at -22°F (-30°C)
130 Seconds Maximum for 0 to 177 lb·in (0 to 20 N·m) at -40°F (-40°C)
Cycles 60,000 Full Stroke Cycles; 1,500,000 repositions
Audible Noise Rating
(AGx, HGx, GGx Models)
Power On (Running) <40 dBA at 39-13/32 in. (1 m)
Power On (Holding) <20 dBA at 39-13/32 in. (1 m)
Power Off
(Spring
Returning)
<55 dBA at 39-13/32 in. (1 m)