Install Instructions

M9208-GGx-x Series Proportional Electric Spring Return Actuators Installation Instructions 7
Wiring
See Figure 9, Figure 10, and Figure 11 to wire the
applicable M9208-GGx-x Series model.
Note: In Master-Slave applications, the slave actuator
lags the master actuator position by a few seconds.
IMPORTANT: Do not install multiple M9208-GGx-x
Series Actuators connected to the same mechanical
load. Master-Slave application of M9208-GGx-x
Series Actuators requires that each actuator be
connected to independent loads.
Figure 9: Control Wiring Diagrams
FIG:M9xxx-GGx_cntrlwi
r
12
34
~
(+)
Y
COM
U
BLK
RED
GRY
ORN
+
+
1
2
34
~
(+)
Y
COM
U
BLK
RED
GRY
ORN
0(4)...20 mA
+
+
500 / 0.25 W
ٛ
DC 0(2)...10 V Control
0(4)...20 mA Control with
External Resistor
AC/DC
24 V
DC 0(2)...10 V
AC/DC
24 V
DC 0(2)...10 V
DC 0(2)...10 V
Master-Slave Application
Y
DC 0(2)...10 V
+
U
+
1
2
34
BLK
RED
GRY
ORN
AC/DC
24 v
~
(+)
DC 0(2)...10 V
COM
+
12
3
4
BLK
RED
GRY
ORN
Figure 10: M9208-GGx-3 Control Wiring
Diagram (Overrides)
12
34
~
Y
COM
U
BLK
RED
GRY
ORN
+
+
Override to MIN position
AC
24 V
DC 0(2)...10 V
DC 0(2)...10 V
A
A Open = MIN Position
A Closed = Normal Operation
12
34
~
Y
COM
U
BLK
RED
GRY
ORN
+
+
Override to MAX position
AC
24 V
DC 0(2)...10 V
DC 0(2)...10 V
C
B Closed = MAX Position
C Closed = Normal Operation
B
1
2
3
4
~
COM
U
BLK
RED
GRY
ORN
+
+
Override to
MIN, MID, MAX positions
0(4)...20 mA Control with
External Resistor
AC
24 V
A
0(4)...20 mA
500 / 0.25 W
B
C
1
2
3
4
~
COM
U
BLK
RED GRY
ORN
+
+
Override to
MIN, MID, MAX positions
0(2)...10 V Control
AC
24 V
A
B
C
DC
0(2)...10 V
Y
FUNCTION
A
B
C
0% ( MIN )
50% ( MID )
100% ( MAX )
NORMAL
FUNCTION
A
B
C
0% ( MIN )
50% ( MID )
100% ( MAX )
NORMAL
Y
Ω
FIG:M9203GGx2(Z)_wir
Figure 11: Auxiliary Switch Wiring Diagram
COM
NC
NO
21
21
23
22
21
22
23
BLK/
RED
BLK/
BLU
BLK/
GRY
COM
NC
NO
24
25
26
WHT/
RED
WHT/
BLU
WHT/
GRY
25
24
24
26
S2
S1
FIG:xxC_switch_wiring