Install Instructions
Table Of Contents
Technical Specifications (Cont.) 
Feedback Signal 
AGD:  135 ohm feedback potentiometer 
AGE:  1,000 ohm feedback potentiometer 
GGx, HGx:  0 to 10 VDC or 2 to 10 VDC for 90° (10 VDC at 1 mA) 
  Corresponds to input signal span selection. 
JGx:  0 to 10 VDC for 90° (10 VDC at 1 mA) 
Auxiliary Switch Rating 
xGC:  Two Single-Pole, Double-Throw (SPDT) switches rated at 24 VAC 
  1.5 A inductive, 3.0 A resistive; 35.0 VA maximum per switch, Class 2 
Mechanical Output 
(Running Torque) 
M9108 Series:  70 lb·in (8 N·m) for one unit; not intended for tandem use 
M9116 Series:  140 lb·in (16 N·m) for one unit 
M9116 (in tandem)  280 lb·in (32 N·m) for two units (GGx, HGx) 
M9124 Series:  210 lb·in (24 N·m) for one unit 
M9124 (in tandem)  420 lb·in (48 N·m) for two units (AGx, GGx, HGx) 
M9132 Series:  280 lb·in (32 N·m) for one unit, 
M9132 (in tandem)  560 lb·in (64 N·m) for two units (AGx, GGx) 
Audible Noise Rating 
45 dBA at 1 m 
Rotation Range 
0 to 90° in 5-degree increments, mechanically limited to 93° 
Rotation Time 
M9108:  30 seconds at 50% rated load, 
  25 to 50 seconds for 0 to 70 lb·in (0 to 8 N·m) 
M9116:  80 seconds at 50% rated load 
  70 to 115 seconds for 0 to 140 lb·in (0 to 16 N·m) 
M9124:  130 seconds at 50% rated load 
  115 to 175 seconds for 0 to 210 lb·in (0 to 24 N·m) 
M9132:  140 seconds at 50% rated load 
  115 to 205 seconds for 0 to 280 lb·in (0 to 32 N·m) 
Electrical Connection 
M9124-, M9132-AGx: 
  1/4 in. spade terminals with pluggable 3-terminal blocks 
All Other Models:  Screw terminals for 22 to 14 AWG; maximum of two 18, 20, or 
  22 AWG per terminal 
Mechanical Connection 
3/8 to 3/4 in. (10 to 20 mm) diameter round shaft or a 3/8 to 5/8 in. (10 to 16 mm) square shaft 
Enclosure 
NEMA 2, IP42 
Ambient Conditions 
Operating:  -4 to 122°F (-20 to 50°C); 0 to 95% RH, noncondensing 
Storage:  -40 to 186°F (-40 to 86°C); 0 to 95% RH, noncondensing 
Dimensions (H x W x D) 
7.09 x 3.94 x 2.54 in. (180 x 100 x 64.5 mm) 
Shipping Weight 
2.9 lb (1.3 kg) 
Agency Compliance 
UL Listed, File E27734, CCN XAPX 
CSA Certified, File LR85083, Class 3221 02 
CE Mark, EMC Directive 89/336/EEC 
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these 
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or 
misuse of its products. 
Controls Group 
507 E. Michigan Street 
P.O. Box 423  Printed in U.S.A
.
Milwaukee, WI 53201  www.johnsoncontrols.co
m
8 M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators Installation Instructions 