Install Instructions
Table Of Contents
3.  Connect the input control signal: 
•  Terminal 102 from the master actuator to 
Terminal 102 on the slave actuator. 
•  For AGx models, connect the input control 
signal to the common, CW, and CCW terminals 
on both the master and the slave actuators. 
(See Figure 7.) 
•  Terminal 103 from the master actuator to 
Terminal 103 on the slave actuator. 
b.  When mounting two actuators back-to-back on 
the same shaft, connect: 
•  For GGx and HGx models, connect the 
control signal to the master actuator, and 
connect 24 VAC/VDC power to both the master 
and slave actuators. 
•  Terminal 101 from the master actuator to 
Terminal 102 on the slave actuator. 
•  Terminal 102 from the master actuator to 
Terminal 101 on the slave actuator. 
IMPORTANT:  For proper tandem operation, 
do not connect the control input to the slave unit. 
•  Terminal 103 from the master actuator to 
Terminal 103 on the slave actuator. 
Note:  Set the master actuator jumpers on the GGx 
and HGx models according to the action and signal 
range desired before proceeding. (Refer to Figure 8 
and the Setup and Adjustments, Calibration section.) 
The total wire length for these connections may be up 
to 30 ft (9 m). 
Auxiliary Switches
(See Figure 5.)
1 Common
2 Power
3 Calibration Ouput
 (HGx Models Only)
4 Current Input
5 Voltage Input
6 Feedback Output
Span Potentiometer
Zero Potentiometer
Note:
Jumpers W1, W2, W3, and W4
have no effect when the actuator
is in the Slave mode.
Master/Slave Jumper
(Shown in the
Master position)
Term i na l
Block 1
101 102 103
 1 2 3 4 5 6  
Jumper W2
Factory Set
Voltage Input
 0 to 10 VDC
Current Input
Feedback Ouput
 0 to 20 mA  4 to 20 mA
2 to10 VDC
* HGx Models Only
Fixed
Jumper W3*
Factory Set
Adjustable
Jumper W1
Direct Acting (DA)
Reverse Acting (RA)
Rotation Direction with
Increasing Signal
Factory Set
(CCW) RA
(CW) DA
Feedback Output
Factory Set
Voltage Input
Jumper W4
Note:
For current input, 
set Jumper W4
in the 0 to 10 VDC 
position.
101
Termin a l
Block 1
103102
4.  Make sure of the following if the actuators 
configured for tandem operation stall or fail to 
drive: 
a.  Both actuators have the same torque and 
control input. 
b.  One actuator is set as the master and the other 
as the slave. 
c.  The control signal is connected to the master 
actuator only. 
d.  Terminal 101, Terminal 102, and Terminal 103 
are connected properly, as described in Step 2. 
Setup and Adjustments 
Calibration 
Calibrate only the actuator designated as the master 
when using two AGx, GGx, or HGx models in 
tandem. 
Direction of Action 
In the DA mode (factory set), a minimum control signal 
drives the actuator to the full CCW position, and a 
maximum control signal drives it fully CW. In the 
Reverse Acting (RA) mode, a minimum control signal 
drives the actuator to the full CW position, and a 
maximum control signal drives it fully CCW. To set an 
actuator for RA, proceed to the section for the 
appropriate model. 
IMPORTANT:  Adjust the rotation range before 
changing the direction of action. 
Figure 8: Settings on GGx and HGx Models 
M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators Installation Instructions 5 