Through the Conduit Openings 
Depending on the M91xx Series model selected, use 
one or both conduit openings. The threaded actuator 
conduit openings accept 1/2 in. trade size conduit 
fittings. Refer to Figure 6 and proceed as follows: 
Models with the same torque and control input may be 
mounted in tandem. For example: 
•  M9116: two GGx, two HGx, or one GGx and 
one HGx 
1.  Loosen the cover screw with a Phillips No. 1 
screwdriver, and remove the actuator cover. 
•  M9124: two AGx, two GGx, two HGx, or one GGx 
and one HGx 
Plugs
(Conduit Openings)
Cover
Screw
•  M9132: two AGx or two GGx 
Note:  Do not use M9108 Series models in 
tandem. 
The Master/Slave Jumper is factory set in the master 
position. Determine the method for mounting the two 
actuators in tandem: front-to-back (Figure 7 shows the 
front view) or back-to-back, and proceed as follows: 
Figure 6: Location of the Conduit Openings 
2.  Push the plastic plug out of the conduit opening 
with fingertip. 
Common
CW
CCW
Terminal 101
Terminal 102
Terminal 103
Master/Slave
Jumper
(Shown in the
Master Position)
Spade Terminals for
Feedback Potentiometer
on AGD or AGE and
Auxiliary Switches on AGC
(See Figure 5.)
Terminal Block 1
Terminal Block 2
3.  Use the Phillips screwdriver to puncture a hole 
through the center of the plug, and reinsert the 
plug into the conduit opening. 
Note:  For applications requiring metal conduit, 
thread the conduit fitting into the conduit opening and 
hand tighten. 
IMPORTANT:  Use flexible metallic tubing or its 
equivalent with the fitting. Do not overtighten the 
conduit fitting into the actuator to avoid damaging 
the actuator threads. 
4.  Insert the cable wires through the plastic plug or 
conduit fitting, and connect to the terminal block 
using the applicable wiring diagrams in Figure 5. 
5.  Perform the procedures appropriate to the specific 
application, as described in the Tandem Operation 
and Setup and Adjustments sections. 
Figure 7: Settings on AGx Models 
6.  Reattach the cover and tighten the cover screw. 
1.  Designate one actuator as the master, and move 
Master/Slave Jumper on the other actuator to the 
slave position. 
Tandem Operation 
The tandem configuration provides twice the torque of 
a single actuator as follows: 
2.  Connect Terminal 101, Terminal 102, and 
Terminal 103 from the master actuator to the 
corresponding terminals on the slave actuator. 
(Refer to Figure 7 for AGx models and Figure 8 for 
GGx and HGx models.) 
•  280 lb·in (32 N·m) for two M9116-GGx or 
M9116-HGx units 
•  420 lb·in (48 N·m) for two M9124-GGx or 
M9124-HGx units 
a.  When mounting two actuators front-to-back on 
the same shaft, connect: 
•  560 lb·in (64 N·m) for two M9132-GGx or 
M9132-HGx units 
•  Terminal 101 from the master actuator to 
Terminal 101 on the slave actuator. 
The actuators operate in exact synchronization, 
ensuring the load is split evenly between each unit. 
4 M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators Installation Instructions 