505429-JTG-F-1010 Description Series 20 condensing units and heat pumps are completely assembled, piped and wired at the factory to provide a single-piece unit for shipment and rigging. Each unit is pressurized with a holding charge of refrigerant R-410A for storage and/or shipping.
505429-JTG-F-1010 Table of Contents Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
505429-JTG-F-1010 Nomenclature Configured Split Condenser Model Number Nomenclature J20 Y C C00 A 2 A AA 2 A Product Style Nominal Cooling Capacity - MBH A = Style A J07 = 7.5 Ton J10 = 10 Ton J12 = 12.
505429-JTG-F-1010 Condensing Unit Features and Benefits • Factory installed powered or non-powered 115 volt GFI outlet. Features • Factory installed phase monitor to protect the unit from phase loss or phase reversal. • Meets or exceeds ASHRAE 90.1 standards. • Scroll compressors provide both high efficiency and reliability. • Simplicity ® Controls • Dual refrigerant circuits on J**PD and J**YD models.
05429-JTG-F-1010 Air Handling Unit Features and Benefits Features These air handlers can be arranged for a variety of air discharge patterns in either the horizontal or vertical position. Refer to the unit installation instructions for other application possibilities. Benefits Air handling units are designed with two distinct modules to provide maximum application flexibility. All are shipped as single packages with the blower module mounted on top of the coil module.
505429-JTG-F-1010 been mechanically expanded into aluminum fins. Both headers are located on the same end of the coil. The coil is leak-tested at 325 psig and dried before the connections are capped for storage and shipping.
505429-JTG-F-1010 Condenser Motors • Totally enclosed, air over cooled. • Inherent overload protection. flashes a fault code that indicates which safety switch has tripped. Non-fused Disconnect Switch • Permanently lubricated bearings. • Factory-installed, internally mounted. • Must cycle to allow cooling operation down to 40°F. • Accessible from outside the unit. Refrigerant Piping • Solid core filter-drier(s) ship loose for field installation.
505429-JTG-F-1010 Each Unit Enclosure Shall Have: • Exterior panels of 18 gauge steel, finished with baked enamel to provide a long lasting quality appearance • Removable panels to provide easy access to the internal components for maintenance and service on condensing units, heat pumps and air handlers • Air handling units must have a filter rack that accepts both 2” and 4” filters. • The dimensions of each unit shall not exceed those specified in the manufacture’s literature.
505429-JTG-F-1010 Physical Data J07 - 25YC and J10 - 20YD Physical Data Component Nominal Tonnage REFRIGERANT Refrigerant type Holding charge (lb)1 (each system) System #1 Operating Charge (lb)2 System #2 DIMENSIONS (inches) Length Width Height WEIGHTS (lb) Shipping Operating COMPRESSORS3 Type Quantity Nominal Capacity (Tons) Capacity Stages System #1 System #2 System #1 System #2 SYSTEM DATA No. Refrigeration Circuits Suction Line OD (in.) Liquid Line OD (in.) OUTDOOR COIL DATA Face area (Sq. Ft.
505429-JTG-F-1010 J07 - 20PC and J15 - 20PD Physical Data Models Component J07PC 7.5 J10PC 10 J15PC 15 J15PD 15 J20PC 20 J20PD 20 R-410A 1.0 23.9 --- R-410A 1.0 27.5 --- R-410A 1.0 54.0 --- R-410A 1.0 27.0 27.0 R-410A 1.0 60.0 --- R-410A 1.0 34.0 34.0 59.1 31.9 44.5 59.1 31.9 50.0 59.1 64.1 44.5 59.1 64.1 44.5 59.1 64.1 50.0 59.1 64.1 50.
505429-JTG-F-1010 J07 - 20NC and J10 - 20ND Indoor Unit Physical Data J07NC 7 1/2 J10NC 10 J10ND 10 Models J15NC 15 J15ND 15 J20NC 20 J20ND 20 Length 56.0 56.0 56.0 74.5 74.5 98.5 98.5 Width 30.0 30.0 30.0 33.0 33.0 30.0 30.0 Height 65.0 65.0 65.0 75.0 75.0 65.0 65.0 526 573 575 796 796 938 938 Standard Motor and Drive 498 539 541 764 764 873 873 High Static Motor and Drive INDOOR BLOWER (Forward Curve) Diameter x Width Quantity INDOOR COIL Face area (Sq. Ft.
505429-JTG-F-1010 J25NC Indoor Unit Physical Data Component Nominal Tonnage DIMENSIONS (inches) Models J25NC 25 Length 100.1 Width 38.1 74.6 Height WEIGHTS1 (lb) Unit Shipping 1067 Unit Operating With 5 hp Motor and Drive 1130 7.5 hp Motor and Drive INDOOR BLOWER (Forward Curve) Diameter x Width Quantity INDOOR COIL Face area (Sq. Ft.) Rows Fins per inch Tube diameter Circuitry Type Refrigerant Control SYSTEM DATA No. Refrigeration Circuits Suction Line OD (in.) Liquid Line OD (in.
505429-JTG-F-1010 Unit Limitations Condenser Unit limitations Size (Tons) Model J07 (7.5) PC J07 (7.5) YC J10 (10) PC J10 (10) YC/YD J12 (12.
505429-JTG-F-1010 Air Handling Unit Limitations Entering Air Temperature Degrees °F Model J07NC J10NC J10ND J15NC J15ND J20NC J20ND J25NC 1 14 Power Supply Voltage Voltage Variation Supply Air Range CFM Cooling DB/WB Heating DB1 Min. Max. Min. Max. Min. Max. Min. Max.
505429-JTG-F-1010 Cooling and Heating Ratings Cooling And Heating Rating System Cooling Capacity1 Condensing Unit Only Outdoor Unit Gross Capacity2 (MBH) KW EER Indoor Unit Heating Capacity1 High Outdoor Gross Capacity3 (MBH) EER IEER IPLV Low Outdoor Gross Capacity2 (MBh) COP Gross Capacity2 (MBh) COP Rated Airflow (CFM) J07PC4 N/A N/A N/A J07NC 92 11.0 11.4 --- 82 3.3 49 2.3 J10PC4 N/A N/A N/A J10NC 124 11.0 11.4 11.8 109 3.3 63 2.
505429-JTG-F-1010 Capacity Performance Condenser and Air Handling Cooling Capacities J07YC/J07NC Air on Evaporator Coil CFM 2250 2625 3000 3375 3750 2250 2625 3000 3375 3750 16 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 110.8 103.3 95.9 88.0 77.7 114.0 106.3 98.7 90.6 79.9 117.2 109.3 101.4 93.1 82.2 109.2 101.3 93.0 82.1 109.1 101.2 92.9 82.0 6.0 5.7 5.5 5.4 5.2 6.0 5.7 5.4 5.4 5.2 5.9 5.7 5.4 5.4 5.2 5.8 5.5 5.5 5.
505429-JTG-F-1010 J07YC/J07NC (Continued) Air on Evaporator Coil CFM 2250 2625 3000 3375 3750 1 2 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 94.7 87.8 80.9 74.3 75.0 97.0 89.9 82.8 76.1 76.8 99.2 92.0 84.8 77.8 78.6 92.2 84.9 78.0 78.7 92.3 85.1 78.1 78.9 9.0 9.1 9.1 8.8 8.9 9.1 9.1 9.2 8.8 9.0 9.1 9.2 9.2 8.9 9.0 9.2 9.2 8.9 9.0 9.1 9.2 8.9 9.
505429-JTG-F-1010 J07YC/J10NC Air on Evaporator Coil CFM 2250 2625 3000 3375 3750 2250 2625 3000 3375 3750 18 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 105.1 100.1 95.1 87.9 83.1 109.8 104.5 99.3 91.8 86.7 114.5 109.0 103.5 95.7 90.4 110.2 104.6 96.7 91.4 111.4 105.8 97.8 92.4 6.0 5.8 5.7 5.6 5.5 6.0 5.9 5.7 5.6 5.6 6.1 5.9 5.8 5.7 5.6 6.0 5.8 5.7 5.6 6.0 5.9 5.7 5.7 49.2 63.3 77.3 87.9 83.1 53.6 68.6 83.5 91.
505429-JTG-F-1010 J07YC/J10NC (Continued) Air on Evaporator Coil CFM 2250 2625 3000 3375 3750 1 2 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 103.1 95.4 87.6 80.6 79.5 106.1 98.2 90.3 83.0 81.8 109.2 101.0 92.9 85.4 84.2 103.1 94.7 87.1 85.9 105.1 96.6 88.8 87.6 9.1 9.0 8.9 8.7 8.6 9.2 9.1 9.0 8.8 8.7 9.3 9.2 9.1 8.9 8.8 9.2 9.1 9.0 8.8 9.2 9.1 9.0 8.
505429-JTG-F-1010 J10YC/J10NC Air on Evaporator Coil CFM 3000 3500 4000 4500 5000 3000 3500 4000 4500 5000 20 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 142.3 133.9 125.5 115.0 111.2 151.4 142.4 133.4 122.3 118.3 160.5 150.9 141.4 129.6 125.4 154.4 144.7 132.6 128.3 157.9 148.0 135.6 131.2 7.5 7.4 7.3 7.3 7.2 7.5 7.4 7.3 7.3 7.2 7.5 7.4 7.3 7.3 7.2 7.5 7.4 7.3 7.3 7.5 7.4 7.3 7.3 64.7 84.4 104.0 115.0 111.2 72.
505429-JTG-F-1010 J10YC/J10NC (Continued) Air on Evaporator Coil CFM 3000 3500 4000 4500 5000 1 2 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 117.5 109.1 100.8 94.0 94.0 124.2 115.4 106.6 99.4 99.4 131.0 121.7 112.3 104.8 104.8 124.7 115.2 107.4 107.4 127.8 118.0 110.1 110.1 12.0 11.9 11.9 11.8 11.8 12.0 11.9 11.9 11.8 11.8 12.0 11.9 11.9 11.8 11.8 11.9 11.9 11.8 11.8 12.0 11.9 11.8 11.9 63.4 81.0 98.6 94.0 94.0 74.
505429-JTG-F-1010 J10YD/J10ND Air on Evaporator Coil CFM 3000 3500 4000 4500 5000 3000 3500 4000 4500 5000 22 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 138.1 130.1 122.0 112.3 108.2 147.1 138.4 129.8 119.5 115.1 156.0 146.8 137.7 126.8 122.1 152.4 142.9 131.5 126.7 157.9 148.1 136.3 131.3 7.5 7.4 7.2 7.2 7.1 7.5 7.4 7.3 7.2 7.2 7.6 7.4 7.3 7.2 7.2 7.5 7.3 7.2 7.2 7.5 7.4 7.3 7.3 63.6 82.9 102.2 112.3 108.2 70.
505429-JTG-F-1010 J10YD/J10ND (Continued) Air on Evaporator Coil CFM 3000 3500 4000 4500 5000 1 2 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 116.8 106.7 96.6 89.7 93.0 122.7 112.1 101.4 94.2 97.7 128.6 117.4 106.3 98.8 102.3 122.9 111.2 103.3 107.1 128.3 116.1 107.9 111.8 12.1 11.9 11.8 11.7 11.7 12.1 11.9 11.8 11.7 11.7 12.1 11.9 11.8 11.7 11.7 12.0 11.8 11.7 11.7 12.0 11.9 11.7 11.8 58.7 75.9 93.2 89.7 93.0 71.
505429-JTG-F-1010 J12YC/J15NC Air on Evaporator Coil CFM 3750 4375 5000 5625 6250 3750 4375 5000 5625 6250 24 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 178.5 168.2 157.9 144.8 149.7 184.7 174.0 163.4 149.9 154.9 190.9 179.9 168.8 154.9 160.1 182.3 171.1 157.0 162.2 184.7 173.4 159.0 164.4 10.2 9.9 9.6 9.4 9.5 10.2 9.9 9.6 9.4 9.5 10.3 9.9 9.6 9.4 9.6 10.1 9.8 9.6 9.7 10.2 9.9 9.7 9.8 87.6 111.9 136.1 144.8 149.
505429-JTG-F-1010 J12YC/J15NC (Continued) Air on Evaporator Coil CFM 3750 4375 5000 5625 6250 1 2 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 153.8 142.2 130.5 128.2 131.2 155.5 143.8 132.0 129.7 132.7 157.3 145.4 133.5 131.1 134.2 149.5 137.3 134.8 138.0 153.6 141.0 138.5 141.8 15.8 15.5 15.1 15.1 15.2 15.7 15.3 15.0 15.0 15.1 15.5 15.2 14.9 14.9 15.0 15.4 15.1 15.1 15.2 15.6 15.3 15.3 15.4 77.6 101.0 124.4 128.
505429-JTG-F-1010 J12YD/J15ND Air on Evaporator Coil CFM 3750 4375 5000 5625 6250 3750 4375 5000 5625 6250 26 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 170.2 164.1 157.9 142.4 141.3 182.4 175.5 168.7 152.3 151.2 194.5 187.0 179.5 162.2 161.1 187.6 180.3 162.8 161.6 188.2 181.0 163.3 162.1 10.0 9.7 9.5 9.3 9.3 10.0 9.7 9.5 9.4 9.3 10.0 9.8 9.5 9.4 9.4 9.8 9.6 9.5 9.4 9.9 9.7 9.5 9.5 80.1 106.1 132.0 142.4 141.
505429-JTG-F-1010 J12YD/J15ND (Continued) Air on Evaporator Coil CFM 3750 4375 5000 5625 6250 1 2 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 148.6 138.6 128.6 119.7 123.4 155.4 145.0 134.5 125.3 129.1 162.3 151.3 140.4 130.8 134.8 154.3 143.2 133.4 137.4 157.3 146.0 136.0 140.1 15.3 15.1 14.8 14.5 14.7 15.4 15.1 14.8 14.5 14.7 15.4 15.1 14.8 14.5 14.7 15.2 14.9 14.6 14.8 15.3 15.0 14.7 14.9 73.8 97.6 121.5 119.
505429-JTG-F-1010 J15YC/J15NC Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 4500 5250 6000 6750 7500 28 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 223.5 207.2 191.0 176.0 175.0 229.4 212.8 196.1 180.7 179.7 235.4 218.3 201.2 185.4 184.4 221.3 204.0 187.9 186.8 224.2 206.7 190.4 189.3 11.8 11.5 11.1 10.8 10.8 11.9 11.6 11.2 11.0 10.9 12.0 11.7 11.3 11.1 11.0 11.3 11.0 10.7 10.6 10.9 10.6 10.3 10.3 104.
505429-JTG-F-1010 J15YC/J15NC (Continued) Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 1 2 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 185.3 170.5 155.8 145.5 147.3 189.1 174.1 159.0 148.5 150.4 192.9 177.6 162.2 151.5 153.4 179.0 163.5 152.7 154.7 180.4 164.8 153.9 155.9 17.5 17.3 17.1 16.9 16.8 17.6 17.4 17.2 17.0 16.9 17.7 17.5 17.3 17.0 17.0 17.5 17.3 17.0 17.0 17.5 17.3 17.0 17.0 92.7 119.4 146.1 145.
505429-JTG-F-1010 J15YC/J20NC Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 4500 5250 6000 6750 7500 30 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 214.3 201.7 189.0 181.2 177.1 220.7 207.6 194.6 186.5 182.3 227.1 213.6 200.2 191.9 187.6 218.3 204.5 196.0 191.6 223.0 208.9 200.2 195.7 12.1 11.8 11.6 11.3 11.3 12.2 11.9 11.7 11.4 11.4 12.3 12.0 11.8 11.5 11.5 12.1 11.9 11.6 11.6 12.2 11.9 11.7 11.6 111.
505429-JTG-F-1010 J15YC/J20NC (Continued) Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 1 2 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 203.2 187.4 171.6 153.7 157.8 208.6 192.4 176.2 157.8 162.0 214.1 197.4 180.8 162.0 166.3 200.5 183.6 164.5 168.8 203.6 186.4 167.0 171.4 18.8 18.3 17.7 17.2 17.1 19.0 18.4 17.8 17.3 17.2 19.1 18.5 17.9 17.4 17.3 18.5 17.9 17.4 17.3 18.5 17.9 17.4 17.3 106.1 131.7 157.3 153.
505429-JTG-F-1010 J15YD / Two J07NC Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 4500 5250 6000 6750 7500 32 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 216.0 200.4 184.8 173.1 165.6 222.3 206.2 190.2 178.1 170.4 228.6 212.1 195.6 183.2 175.2 216.4 199.6 186.9 178.8 220.7 203.5 190.6 182.4 12.0 11.7 11.4 11.2 11.1 12.1 11.8 11.5 11.2 11.2 12.1 11.9 11.6 11.3 11.3 11.9 11.6 11.4 11.3 12.0 11.7 11.4 11.
505429-JTG-F-1010 J15YD / Two J07NC (Continued) Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 1 2 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 193.0 179.5 166.0 154.6 151.8 198.9 185.0 171.0 159.2 156.4 204.7 190.4 176.1 163.9 161.0 192.4 177.9 165.6 162.6 194.3 179.7 167.3 164.3 17.7 17.4 17.1 16.8 16.8 17.8 17.5 17.2 16.9 16.9 17.9 17.6 17.2 17.0 17.0 17.6 17.3 17.1 17.0 17.7 17.4 17.1 17.1 96.7 121.8 146.
505429-JTG-F-1010 J15YD / Two J10NC Air on Evaporator Coil CFM 6000 7000 8000 9000 10000 6000 7000 8000 9000 10000 34 Temperature of Air on Condenser Coil Sensible Capacity (MBh)1 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 241.0 222.0 203.0 191.6 189.3 247.3 227.8 208.3 196.6 194.3 253.6 233.6 213.6 201.6 199.3 238.5 218.1 205.8 203.4 243.3 222.5 210.0 207.6 12.0 11.7 11.4 11.2 11.2 12.1 11.8 11.5 11.2 11.3 12.
505429-JTG-F-1010 J15YD / Two J10NC (Continued) Air on Evaporator Coil CFM 6000 7000 8000 9000 10000 1 2 Temperature of Air on Condenser Coil Sensible Capacity (MBh)1 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 226.4 210.6 194.9 185.6 185.6 228.3 212.4 196.5 187.1 187.1 230.2 214.2 198.2 188.7 188.7 216.2 200.1 190.5 190.5 218.3 202.0 192.3 192.3 15.9 15.6 15.3 15.0 15.0 17.1 16.8 16.5 16.2 16.2 18.3 18.0 17.7 17.
505429-JTG-F-1010 J15YD/J15ND Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 4500 5250 6000 6750 7500 36 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 208.6 198.3 188.0 170.5 177.8 217.2 206.4 195.7 177.6 185.1 225.8 214.6 203.4 184.6 192.4 214.6 203.4 184.6 192.4 214.6 203.5 184.6 192.5 11.7 11.4 11.0 10.9 11.0 11.7 11.4 11.1 10.9 11.0 11.8 11.4 11.1 11.0 11.1 11.5 11.2 11.1 11.1 11.6 11.3 11.1 11.2 106.
505429-JTG-F-1010 J15YD/J15ND (Continued) Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 175.1 163.9 152.8 144.6 146.8 181.4 169.9 158.3 149.8 152.1 187.8 175.8 163.9 155.1 157.5 174.6 162.8 154.0 156.4 173.5 161.7 153.0 155.4 17.7 17.4 17.2 17.1 17.0 17.7 17.5 17.2 17.1 17.0 17.8 17.5 17.3 17.2 17.1 17.6 17.3 17.2 17.1 17.6 17.3 17.2 17.1 89.8 117.8 145.9 144.6 146.
505429-JTG-F-1010 J15YD/J20ND Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 4500 5250 6000 6750 7500 38 Temperature of Air on Condenser Coil Sensible Capacity (MBh)1 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 213.8 201.0 188.1 171.4 175.2 220.6 207.3 194.1 176.8 180.7 227.3 213.6 200.0 182.2 186.3 217.5 203.6 185.5 189.6 221.4 207.3 188.8 193.0 12.1 11.8 11.5 11.3 11.3 12.2 11.9 11.6 11.4 11.4 12.3 12.
505429-JTG-F-1010 J15YD/J20ND (Continued) Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 1 2 Temperature of Air on Condenser Coil Sensible Capacity (MBh)1 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 200.6 186.0 171.4 153.0 156.4 207.4 192.3 177.2 158.2 161.8 214.3 198.7 183.1 163.5 167.1 200.5 184.7 164.9 168.6 202.3 186.4 166.4 170.1 18.3 17.8 17.4 16.9 16.9 18.4 18.0 17.5 17.0 17.0 18.6 18.1 17.6 17.1 17.
505429-JTG-F-1010 J20YC/J20NC Air on Evaporator Coil CFM 6000 7000 8000 9000 10000 6000 7000 8000 9000 10000 40 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 286.3 267.4 248.5 228.9 227.5 296.6 277.0 257.5 237.1 235.7 306.9 286.6 266.4 245.4 243.8 296.2 275.2 253.5 251.9 305.7 284.0 261.7 260.0 15.3 14.8 14.4 14.1 14.0 15.4 14.9 14.5 14.2 14.1 15.5 15.0 14.6 14.3 14.2 15.1 14.7 14.4 14.3 15.2 14.8 14.5 14.4 136.
505429-JTG-F-1010 J20YC/J20NC (Continued) Air on Evaporator Coil CFM 6000 7000 8000 9000 10000 1 2 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 244.4 226.2 208.0 192.2 194.4 250.0 231.4 212.8 196.7 198.9 255.7 236.6 217.6 201.1 203.3 241.9 222.4 205.6 207.9 247.2 227.3 210.0 212.4 23.4 22.8 22.1 21.6 21.8 23.5 22.8 22.1 21.7 21.8 23.5 22.8 22.2 21.7 21.8 23.0 22.3 21.9 22.0 23.2 22.5 22.0 22.2 120.7 156.5 192.4 192.
505429-JTG-F-1010 J20YD / Two J10NC Air on Evaporator Coil CFM 6000 7000 8000 9000 10000 6000 7000 8000 9000 10000 42 Temperature of Air on Condenser Coil Sensible Capacity (MBh)1 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 268.6 253.5 238.3 214.5 213.5 280.9 265.0 249.1 224.2 223.1 293.1 276.4 259.8 234.0 232.8 278.2 261.5 235.5 234.3 280.0 263.2 236.9 235.7 15.0 14.6 14.2 13.9 13.9 15.1 14.7 14.3 14.0 14.0 15.
505429-JTG-F-1010 J20YD / Two J10NC (Continued) Air on Evaporator Coil CFM 6000 7000 8000 9000 10000 1 2 Temperature of Air on Condenser Coil Sensible Capacity (MBh)1 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 193.7 205.5 217.3 200.0 183.4 208.6 221.4 234.1 215.5 197.5 223.6 237.2 250.9 230.9 211.7 246.6 260.8 240.1 220.1 256.0 270.8 249.2 228.5 16.1 19.1 22.1 21.7 21.4 16.3 19.3 22.3 22.0 21.7 16.5 19.6 22.6 22.
505429-JTG-F-1010 J20YD/J20ND Air on Evaporator Coil CFM 6000 7000 8000 9000 10000 6000 7000 8000 9000 10000 44 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 292.8 272.9 253.0 231.8 224.6 302.2 281.7 261.1 239.3 231.8 311.7 290.5 269.3 246.8 239.1 299.4 277.5 254.3 246.4 308.2 285.7 261.9 253.7 14.7 14.4 14.0 13.8 13.7 14.8 14.5 14.2 13.9 13.9 14.9 14.6 14.3 14.0 14.0 14.9 14.6 14.3 14.2 15.2 14.8 14.6 14.5 136.
505429-JTG-F-1010 J20YD/J20ND (Continued) Air on Evaporator Coil CFM 6000 7000 8000 9000 10000 1 2 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 249.8 229.9 210.1 198.2 196.0 255.8 235.5 215.2 203.0 200.8 261.9 241.1 220.3 207.8 205.5 246.6 225.3 212.6 210.3 252.2 230.4 217.4 215.0 22.6 22.3 22.0 21.9 21.9 22.7 22.4 22.1 22.0 22.0 22.8 22.5 22.2 22.1 22.1 22.7 22.4 22.3 22.3 23.0 22.7 22.5 22.5 126.1 160.6 195.1 198.
505429-JTG-F-1010 J25YC/J25NC Air on Evaporator Coil CFM 7500 8750 10000 11250 12500 7500 8750 10000 11250 12500 46 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 390.0 360.6 331.2 305.3 308.5 399.4 369.3 339.2 312.8 316.1 408.8 378.0 347.2 320.3 323.7 390.1 358.3 330.5 334.0 402.1 369.4 340.7 344.3 20.3 19.9 19.5 18.6 18.5 20.7 20.4 20.0 19.0 18.9 21.2 20.8 20.4 19.4 19.3 20.5 20.2 19.2 19.1 20.3 19.9 18.9 18.
505429-JTG-F-1010 J25YC/J25NC (Continued) Air on Evaporator Coil CFM 7500 8750 10000 11250 12500 1 2 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 317.1 288.5 259.8 246.4 258.8 318.9 290.1 261.3 247.8 260.2 320.7 291.7 262.7 249.2 261.7 302.2 272.2 258.2 271.1 312.8 281.7 267.2 280.6 31.5 30.8 30.2 29.7 29.6 31.6 31.0 30.4 29.9 29.7 31.8 31.2 30.5 30.0 29.9 31.2 30.5 30.0 29.9 31.2 30.6 30.0 29.9 143.2 194.6 246.1 246.
505429-JTG-F-1010 Condenser Only Cooling Capacities Condenser Only Ratings Suction Press. Temperature of Air on Condenser Coil °F and Model 65 75 85 95 105 115 Corresponding Temp.
505429-JTG-F-1010 Heat Pump and Air Handling Cooling Capacities J07PC/J07NC Cooling Capacities Air on Evaporator Coil CFM 2250 2625 3000 3375 3750 2250 2625 3000 3375 3750 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 112.8 104.8 96.7 89.0 88.9 117.0 108.6 100.3 92.3 92.2 121.1 112.5 103.8 95.6 95.4 114.6 105.7 97.4 97.2 116.6 107.7 99.1 99.0 5.9 5.8 5.7 5.5 5.6 5.9 5.8 5.7 5.6 5.6 5.9 5.8 5.7 5.6 5.6 5.8 5.7 5.6 5.
5429-JTG-F-1010 J07PC/J07NC Cooling Capacities (Continued) Air on Evaporator Coil CFM 2250 2625 3000 3375 3750 1 2 50 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 99.8 86.5 73.1 69.9 69.5 103.0 89.2 75.5 72.1 71.7 106.2 92.0 77.8 74.4 73.9 94.8 80.2 76.7 76.2 97.7 82.6 79.0 78.5 8.8 8.7 8.7 8.5 8.5 8.8 8.8 8.7 8.6 8.6 8.9 8.8 8.7 8.6 8.6 8.8 8.8 8.6 8.6 8.8 8.8 8.7 8.6 69.7 71.4 73.1 69.9 69.5 82.4 78.9 75.5 72.
505429-JTG-F-1010 J10PC/J10NC Air on Evaporator Coil CFM 3000 3500 4000 4500 5000 3000 3500 4000 4500 5000 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 140.5 133.6 126.6 120.2 121.8 147.3 140.0 132.8 126.0 127.7 154.1 146.5 138.9 131.8 133.6 148.2 140.5 133.4 135.2 150.0 142.2 134.9 136.7 7.5 7.5 7.4 7.4 7.3 7.7 7.6 7.6 7.6 7.5 7.8 7.8 7.8 7.8 7.6 7.7 7.7 7.7 7.5 7.6 7.5 7.5 7.4 70.2 87.5 104.8 120.2 121.8 74.8 93.
505429-JTG-F-1010 J10PC/J10NC (Continued) Air on Evaporator Coil CFM 3000 3500 4000 4500 5000 1 2 52 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 113.3 105.2 97.2 95.9 97.1 118.7 110.2 101.8 100.4 101.8 124.1 115.3 106.4 105.0 106.4 116.3 107.3 105.9 107.3 117.2 108.3 106.8 108.2 12.1 12.0 11.9 11.8 11.8 12.2 12.1 12.0 11.9 12.0 12.3 12.2 12.1 12.1 12.1 12.1 12.0 12.0 12.0 12.1 12.0 11.9 11.9 58.5 77.8 97.2 95.9 97.
505429-JTG-F-1010 J15PC/J15NC Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 4500 5250 6000 6750 7500 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 223.0 209.3 195.7 176.7 179.6 229.0 215.0 200.9 181.4 184.5 235.0 220.6 206.2 186.2 189.3 223.2 208.6 188.4 191.6 225.9 211.1 190.6 193.8 12.5 12.3 12.1 11.8 11.8 12.6 12.4 12.2 11.8 11.9 12.6 12.4 12.2 11.9 11.9 12.5 12.3 11.9 12.0 12.6 12.4 12.0 12.1 104.1 134.
505429-JTG-F-1010 J15PC/J15NC (Continued) Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 1 2 54 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 175.1 162.0 148.8 138.1 143.6 179.2 165.7 152.3 141.3 146.9 183.2 169.5 155.8 144.5 150.2 171.9 158.0 146.6 152.4 174.3 160.2 148.6 154.5 18.3 18.1 18.0 17.8 17.8 18.3 18.1 18.0 17.8 17.8 18.3 18.1 18.0 17.8 17.9 18.2 18.0 17.8 17.9 18.2 18.1 17.9 18.0 92.4 120.0 147.6 138.
505429-JTG-F-1010 J15PD/J15ND Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 4500 5250 6000 6750 7500 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 231.4 215.6 199.7 183.7 184.6 233.6 217.6 201.6 185.5 186.3 235.8 219.7 203.5 187.2 188.0 222.5 206.2 189.7 190.5 225.4 208.9 192.1 193.0 12.4 12.0 11.7 11.4 11.4 12.4 12.1 11.7 11.4 11.4 12.4 12.1 11.7 11.4 11.4 12.1 11.8 11.5 11.5 12.2 11.8 11.5 11.5 111.6 142.
505429-JTG-F-1010 J15PD/J15ND (Continued) Air on Evaporator Coil CFM 4500 5250 6000 6750 7500 1 2 56 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 175.7 162.2 148.6 141.5 144.4 177.4 163.7 150.0 142.9 145.8 179.0 165.2 151.4 144.2 147.1 167.3 153.3 146.0 149.0 169.4 155.3 147.9 150.9 18.9 18.6 18.2 18.1 18.1 18.9 18.6 18.3 18.1 18.1 18.9 18.6 18.3 18.1 18.2 18.7 18.3 18.1 18.2 18.7 18.4 18.2 18.3 91.5 123.9 148.6 141.
505429-JTG-F-1010 J20PC/J20NC Air on Evaporator Coil CFM 6000 7000 8000 9000 10000 6000 7000 8000 9000 10000 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 291.6 272.3 252.9 232.6 235.8 302.5 282.4 262.3 241.3 244.6 313.4 292.5 271.7 249.9 253.3 302.9 281.3 258.8 262.3 313.2 290.8 267.6 271.3 15.5 15.2 14.9 14.7 14.7 15.5 15.2 15.0 14.8 14.7 15.5 15.2 15.0 14.8 14.7 15.2 14.9 14.7 14.7 15.2 14.9 14.7 14.6 130.3 169.
505429-JTG-F-1010 J20PC/J20NC (Continued) Air on Evaporator Coil CFM 6000 7000 8000 9000 10000 1 2 58 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 233.9 216.2 198.5 187.4 189.8 241.4 223.2 204.9 193.5 195.9 249.0 230.1 211.3 199.5 202.0 237.2 217.8 205.7 208.3 244.3 224.4 211.8 214.5 23.2 22.8 22.4 22.2 22.0 23.4 23.0 22.6 22.3 22.1 23.5 23.1 22.8 22.5 22.3 23.2 22.8 22.5 22.3 23.2 22.9 22.6 22.4 115.1 151.9 188.
505429-JTG-F-1010 J20PD/J20ND Air on Evaporator Coil CFM 6000 7000 8000 9000 10000 6000 7000 8000 9000 10000 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 314.8 285.9 257.1 239.1 239.5 321.1 291.7 262.3 243.9 244.3 327.5 297.5 267.5 248.8 249.2 303.3 272.7 253.6 254.0 309.0 277.8 258.4 258.8 15.1 14.8 14.5 14.2 14.3 15.2 14.9 14.6 14.3 14.5 15.3 15.0 14.8 14.4 14.6 15.2 14.9 14.6 14.7 15.4 15.1 14.7 14.9 142.6 177.
505429-JTG-F-1010 J20PD/J20ND (Continued) Air on Evaporator Coil CFM 6000 7000 8000 9000 10000 1 2 60 WB (°F) Total Capacity1 (MBh) Total Input (kW)2 90 77 72 67 62 57 77 72 67 62 57 77 72 67 62 57 72 67 62 57 72 67 62 57 244.4 222.6 200.8 190.4 198.8 248.3 226.1 204.0 193.4 201.9 252.1 229.6 207.1 196.4 205.1 233.2 210.3 199.4 208.3 236.7 213.5 202.5 211.4 23.6 23.2 22.8 22.5 22.8 23.6 23.2 22.9 22.6 22.8 23.7 23.3 22.9 22.6 22.9 23.5 23.2 22.8 23.1 23.8 23.4 23.1 23.4 120.7 155.5 190.
505429-JTG-F-1010 Heat Pump And Air Handler Heating Capacities J07PC / J07NC Air Over Evaporator Coil CFM DB (°F) 55 2250 70 80 55 3000 70 80 55 3750 70 80 1 Outdoor Temperature (°F @ 72% RH) Capacity1 & kW -10 0 10 20 30 40 50 60 MBH 34.0 39.6 46.2 53.9 62.9 73.5 86.0 100.6 KW 4.9 5.3 5.6 6.0 6.3 6.7 7.0 7.3 MBH 31.0 36.6 43.2 50.9 60.0 70.6 83.0 97.6 KW 5.8 6.1 6.5 6.8 7.1 7.5 7.8 8.2 MBH 28.7 34.3 40.9 48.6 57.7 68.3 80.7 95.3 KW 6.4 6.
505429-JTG-F-1010 J15PC / J15NC Air Over Evaporator Coil CFM DB (°F) 55 4500 70 80 55 6000 70 80 55 70 7500 80 1 Outdoor Temperature (°F @ 72% RH) Capacity1 & kW -10 0 10 20 30 40 50 60 MBH 68.2 80.0 93.8 110.0 129.1 151.5 177.8 208.7 KW 11.8 12.2 12.7 13.2 13.7 14.1 14.6 15.1 MBH 61.5 73.2 87.0 103.2 122.3 144.7 171.0 201.9 KW 13.5 14.0 14.4 14.9 15.4 15.9 16.3 16.8 MBH 57.6 69.3 83.1 99.3 118.4 140.8 167.1 198.0 KW 15.0 15.5 16.0 16.
505429-JTG-F-1010 J20PC / J20NC Air Over Evaporator Coil CFM DB (°F) 55 6000 70 80 55 8000 70 80 55 70 9000 80 1 Outdoor Temperature (°F @ 72% RH) Capacity1 & kW -10 0 10 20 30 40 50 60 MBH 84.3 98.8 115.6 135.0 157.4 183.2 212.9 247.3 KW 13.7 14.4 15.2 15.9 16.6 17.3 18.1 18.8 MBH 90.0 104.5 121.3 140.7 163.1 188.8 218.6 253.0 KW 16.1 16.8 17.6 18.3 19.0 19.7 20.5 21.2 MBH 88.3 102.8 119.6 139.0 161.3 187.1 216.9 251.2 KW 17.8 18.5 19.
505429-JTG-F-1010 Air Handling and Hot Water Coil Accessory Heating Capacity J25NC / 1HW04061 CAPACITY (MBH) UNIT MODEL HOT WATER COIL MODEL J25NC GPM 1HW0406 CFM ENTERING WATER TEMPERATURE MINUS ENTRY AIR TEMPERATURE °F. 70 90 110 130 150 6,000 204 263 325 384 443 8,000 236 304 372 440 508 10,000 265 341 416 492 568 12,000 291 374 457 540 623 50 1 These capacities do not include any blower motor heat. NOTE: Temperature Water Drop (ºF) = (2 X MBH) / GPM.
505429-JTG-F-1010 Airflow Performance J07NC Upflow and Horizontal Airflow Performance J07NC Upflow (CFM) Available External Static Pressure - IWG 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Std. 1.5 HP & Field Supplied Drive 2250 2500 2750 3000 3250 3500 3750 705 741 780 823 1.0 1.1 1.4 1.6 707 735 767 802 842 884 Standard 1.5 HP & Drive 0.8 0.9 1.1 1.3 1.5 1.7 754 777 805 837 872 912 954 0.8 0.9 1.1 1.2 1.4 1.6 1.
505429-JTG-F-1010 J10NC/ND Upflow and Horizontal Airflow Performance J10NC/ND Upflow (CFM) Available External Static Pressure - IWG 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Std. 2 HP & Field Supplied Drive 2500 2750 3000 3250 3500 3750 4000 4250 4500 4750 5000 653 679 707 737 768 801 1.1 1.3 1.5 1.7 1.9 2.1 664 685 709 735 762 792 824 856 Standard 2 HP & Drive 1.0 1.1 1.3 1.5 1.6 1.9 2.1 2.
505429-JTG-F-1010 J15NC/ND Upflow and Horizontal Airflow Performance J15NC/ND Upflow (CFM) 4500 4750 5000 5250 5500 5750 6000 6250 6500 6750 7000 7250 7500 0.2 RPM BHP 0.4 RPM BHP 0.6 RPM BHP Std. 3 HP & Field Supplied Drive 583 592 602 613 577 1.1 625 590 1.2 638 603 1.3 651 617 1.5 664 587 1.4 631 1.6 679 601 1.6 645 1.8 693 616 1.8 660 2.0 710 632 2.1 675 2.3 725 647 2.3 691 2.5 740 1.1 1.2 1.2 1.3 1.4 1.4 1.6 1.7 1.8 2.0 2.9 3.2 3.5 Available External Static Pressure - IWG 0.8 1.0 1.
505429-JTG-F-1010 J20NC/ND Upflow and Horizontal Airflow Performance J20NC/ND Upflow (CFM) Available External Static Pressure - IWG 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Std. 5 HP & Field Supplied Drive 6000 6250 6500 6750 7000 7250 7500 7750 8000 8250 8500 8750 9000 9250 9500 9750 10000 700 712 726 740 754 768 783 799 815 831 2.6 2.8 3.0 3.2 3.4 3.6 3.9 4.1 4.4 4.
505429-JTG-F-1010 J25NC Airflow Performance1 Avaiable External Static Pressure - IWG CFM 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Motor & Drive 7500 7.5 HP Motor & Drive 600 2.04 648 2.50 694 3.00 738 3.54 781 4.08 823 4.63 863 5.16 903 5.66 942 6.10 981 6.49 603 2.17 652 2.63 698 3.13 742 3.67 785 4.22 827 4.76 867 5.29 907 5.79 946 6.24 984 6.62 608 2.
505429-JTG-F-1010 RPM Selection Unit Model HP Max BHP Std. 1.5 J07NC J10NC/ND J15NC/ND J20NC/ND 1 2 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn Fully Open Open Open Open Open Open Closed Motor Sheave Blower Sheave 1VL40 AK69 -1 690 743 796 849 902 955 1 1194 1.73 HS 2 2.30 1VL40 AK56 - 863 929 995 1062 1128 Std. 2 2.30 1VL40 AK74 -1 641 690 739 789 838 887 HS 3 3.45 1VP56 AK84 -1 906 949 992 1035 1078 1121 Std. 3 3.
505429-JTG-F-1010 Additional Static Resistance CFM Wet Indoor1 Coil 2” Filters 2250 2500 2750 3000 3250 3500 3750 3000 3250 3500 3750 4000 4250 4500 4750 5000 4500 4750 5000 5250 5500 5750 6000 6250 6500 6750 7000 7250 7500 0.03 0.03 0.02 0.02 0.01 0.00 0.00 0.08 0.07 0.07 0.06 0.05 0.04 0.03 0.02 0.00 0.07 0.06 0.06 0.06 0.05 0.05 0.05 0.04 0.03 0.03 0.02 0.01 0.00 0.10 0.11 0.11 0.12 0.13 0.14 0.15 0.12 0.13 0.14 0.15 0.16 0.18 0.19 0.21 0.23 0.11 0.11 0.11 0.12 0.12 0.12 0.13 0.14 0.14 0.15 0.16 0.
505429-JTG-F-1010 Additional Static Resistance (Continued) Model J25NC CFM Hot Water Coil Steam Coil 8000 0.06 0.11 9000 0.07 0.14 10000 0.08 0.17 11000 0.09 0.20 12000 0.10 0.23 CFM Static Pressure and Power-Altitude and Temperature Corrections order to use the indoor blower tables for high altitude applications, certain corrections are necessary.
505429-JTG-F-1010 Altitude/Temperature Correction Factors Table Air Temp. 40 50 60 70 80 90 100 0 1.060 1.039 1.019 1.000 0.982 0.964 0.946 1000 1.022 1.002 0.982 0.964 0.947 0.929 0.912 2000 0.986 0.966 0.948 0.930 0.913 0.897 0.880 3000 0.950 0.931 0.913 0.896 0.880 0.864 0.848 4000 0.916 0.898 0.880 0.864 0.848 0.833 0.817 Altitude (Ft.) 5000 0.882 0.864 0.848 0.832 0.817 0.802 0.787 6000 0.849 0.832 0.816 0.801 0.787 0.772 0.758 7000 0.818 0.802 0.787 0.772 0.758 0.744 0.730 8000 0.788 0.772 0.
505429-JTG-F-1010 Drive Selection 1. Determine Upflow or Horizontal supply duct Application. 2. Determine desired airflow. 3. Calculate or measure the amount of external static pressure. 4. Using the operating point, determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower performance table. (Linear interpolation may be necessary.) 5. Noting the RPM and BHP from step 4, locate the appropriate motor and/or drive on the RPM selection table. 6.
505429-JTG-F-1010 Sound Performance Outdoor Sound Power Levels (dB), 60 Hz Size (Tons) J07 (7.5) J10 (10.0) J12 (12.5) J15 (15.0) J20 (20.0) J25 (25.
505429-JTG-F-1010 Electrical Data Electrical Data For Outdoor Models Electrical Data - Outdoor Unit - AC Without Powered Convenience Outlet Compressors Model J07YC J10YC J10YD J12YC J12YD J15YC J15YD J20YC J20YD J25YC 1 2 76 Outdoor Fan Motor Pwr Conv Outlet Qty FLA (each) FLA Minimum Circuit Ampacity1 Maximum Fuse Size (A)2 1/3 2 2.1 - 35.5 45 1/3 2 1.2 - 17.6 25 575-1-60 1/3 2 0.9 - 13.1 20 137 208/230-1-60 3/4 2 3.0 - 46.8 60 14.0 62 460-1-60 3/4 2 1.
505429-JTG-F-1010 Electrical Data - Outdoor Unit - AC With Powered Convenience Outlet Compressors Model J07YC J10YC J10YD J12YC J12YD J15YC J15YD J20YC J20YD J25YC 1 2 Outdoor Fan Motor Pwr Conv Outlet Qty FLA (each) FLA Minimum Circuit Ampacity1 Maximum Fuse Size (A)2 1/3 2 2.1 10.0 45.5 60 1/3 2 1.2 5.0 22.6 30 575-1-60 1/3 2 0.9 4.0 17.1 25 137 208/230-1-60 3/4 2 3.0 10.0 56.8 70 14.0 62 460-1-60 3/4 2 1.6 5.0 28.5 35 10.6 50 575-1-60 3/4 2 1.
505429-JTG-F-1010 Electrical Data - Outdoor Unit - HP Without Powered Convenience Outlet Compressors Model J07PC J10PC J15PC J15PD J20PC J20PD 1 2 Outdoor Fan Motor Pwr Conv Outlet Qty FLA (each) FLA Minimum Circuit Ampacity1 Maximum Fuse Size (A)2 1/3 2 2.1 - 35.5 45 1/3 2 1.2 - 17.6 25 575-1-60 1/3 2 0.9 - 13.1 20 137 208/230-1-60 3/4 2 3.0 - 46.8 60 14.0 62 460-1-60 3/4 2 1.6 - 23.5 30 10.6 50 575-1-60 3/4 2 1.4 - 18.
505429-JTG-F-1010 Electrical Data For Indoor Models Electrical Data - Indoor Units Motor HP Power Supply Supply Blower Motor FLA 208-3-60 5.0 230-3-60 5.2 460-3-60 2.5 575-3-60 2.0 1.5 208-3-60 6.6 230-3-60 6.8 460-3-60 3.4 575-3-60 2.4 2.0 Johnson Controls Unitary Products MCA1 (Amps) Max Fuse2/ Breaker3 Size (Amps) --20.8 33.4 54.2 75.1 --24.1 38.5 62.5 86.6 --12.0 19.2 31.3 43.3 --9.6 15.4 25.0 34.6 6.3 32.3 47.9 74.0 100.1 6.5 36.6 54.6 84.7 114.8 3.1 18.2 27.2 42.2 57.3 2.
505429-JTG-F-1010 Electrical Data - Indoor Units (Continued) Motor HP Power Supply Supply Blower Motor FLA 208-3-60 9.6 230-3-60 9.4 460-3-60 4.7 575-3-60 3.6 3.0 208-3-60 14.0 230-3-60 14.0 460-3-60 7.0 575-3-60 5.2 5.0 80 MCA1 (Amps) Max Fuse2/ Breaker3 Size (Amps) --20.8 33.4 54.2 75.1 104.2 --24.1 38.5 62.5 86.6 120.3 --12.0 19.2 31.3 43.3 60.1 --9.6 15.4 25.0 34.6 48.1 12.0 38.1 53.7 79.8 105.8 116.2 11.8 41.8 59.9 89.9 120.0 132.0 5.9 20.9 29.9 45.0 60.0 66.0 4.5 16.5 23.
505429-JTG-F-1010 Electrical Data - Indoor Units (Continued) Motor HP Power Supply Supply Blower Motor FLA 208-3-60 14.0 230-3-60 14.0 460-3-60 7.0 575-3-60 5.2 208-3-60 230-3-60 460-3-60 575-3-60 16.7 15.2 7.6 6.1 5.0 5.0 208-3-60 21.7 230-3-60 20.0 460-3-60 10.0 575-3-60 7.8 208-3-60 230-3-60 460-3-60 575-3-60 24.2 22.0 11.0 9.0 7.5 7.5 1 2 3 4 5 Electric Heat Option Model KW J20NC/NDC00E None --20 KW 15 32 KW 24 52 KW 39.
505429-JTG-F-1010 Typical Wiring Diagrams Air Conditioning Condensing Units Typical J07YC Wiring Diagram 82 Johnson Controls Unitary Products
505429-JTG-F-1010 Typical J10 - 12YC Wiring Diagram Johnson Controls Unitary Products 83
505429-JTG-F-1010 Typical J10 - 12YD Wiring Diagram 84 Johnson Controls Unitary Products
505429-JTG-F-1010 Typical J15 - 20YC Wiring Diagram Johnson Controls Unitary Products 85
505429-JTG-F-1010 Typical J25YC Wiring Diagram 86 Johnson Controls Unitary Products
505429-JTG-F-1010 Typical J15 - 20YD Wiring Diagram Johnson Controls Unitary Products 87
505429-JTG-F-1010 Heat Pump Units Typical J07PC Wiring Diagram 88 Johnson Controls Unitary Products
505429-JTG-F-1010 Typical J10PC Wiring Diagram Johnson Controls Unitary Products 89
505429-JTG-F-1010 Typical J15 - 20PC Wiring Diagram 90 Johnson Controls Unitary Products
505429-JTG-F-1010 Typical J15 - 20PD Wiring Diagram Johnson Controls Unitary Products 91
505429-JTG-F-1010 Air Handling Units Typical J07NC Wiring Diagram 92 Johnson Controls Unitary Products
505429-JTG-F-1010 Typical J10 thru 20NC Wiring Diagram Johnson Controls Unitary Products 93
505429-JTG-F-1010 Typical J25NC Wiring Diagram 94 Johnson Controls Unitary Products
505429-JTG-F-1010 Typical J10 thru 20ND Wiring Diagram Johnson Controls Unitary Products 95
505429-JTG-F-1010 Weights And Dimensions Corner Weights & Center of Gravity AC/HP Units Model J07PC J10PC J15PC J15PD J20PC J20PD J07YC J10YC J10YD J12YC J12YD J15YC J15YD J20YC J20YD J25YC Weight (lbs.) Shipping Operating 421 430 543 574 947 968 921 942 1116 1152 1090 1126 390 387 499 497 493 490 499 497 493 490 914 909 899 894 945 942 930 927 945 942 Center of Gravity (in.) X Y 17.3 33 16.4 32.3 32.5 33 34 32.5 32.1 30.8 31.2 31.8 17 32.3 17.3 32.3 17.4 32.5 17 32.3 17.4 32.5 32.5 31.5 32.5 31.5 30.
505429-JTG-F-1010 RIGHT REAR FRONT LEFT CONVENIENCE OUTLET A 30.994 2X (Ø 1.375) KNOCKOUT 2X (Ø 0.875) KNOCKOUT 12.126 9.876 4.751 10.000 7.000 3.883 7.000 3.664 24.000 2.933 31.758 1.664 7.000 23.000 7.000 37.000 58.500 FRONT RIGHT SYSTEM 2 2X (Ø 0.875) KNOCKOUT 2X (Ø 1.375) KNOCKOUT 15.53 12.70 10.000 SYSTEM 1 12.000 4.875 6.26 7.52 8.98 REAR 10.60 4.132 2.382 LEFT 1.
505429-JTG-F-1010 REAR RIGHT LEFT FRONT A SYSTEM 2 SYSTEM 1 2X (Ø 1.375) KNOCKOUT 30.994 11.375 2X (Ø 0.875) KNOCKOUT 9.125 4.750 7.000 23.000 4.132 3.913 3.181 1.913 7.000 37.000 64.000 FRONT 7.000 23.000 37.000 7.000 59.000 RIGHT SYSTEM 2 SYSTEM 1 16.133 13.133 17.367 18.867 20.617 22.
505429-JTG-F-1010 Unit Height Dimensions MODEL A J15PC 44.5 J15PD 44.5 J20PC 50.0 J20PD 50.0 J15YC 44.5 J15YD 44.5 J20YC 50.0 J20YD 50.0 J25YC 50.0 PIPING AND ELECTRICAL CONNECTIONS Piping connections are made from the rear of 7.5 thru 12.5 Ton units and the front of 15 thru 20 Ton units. Connections can be made directly to the suction and liquid line service valves. and Piping and Electrical Connection Sizes tables for piping sizes and electrical knockout details.
505429-JTG-F-1010 Corner Weights & Center of Gravity J07 Thru 20NC/ND Units Model Center of Gravity 4 Point Load Location (lbs.) (in.) Shipping Operating X Y A B C D 6 Point Load Location (lbs.) Weight (lbs.) Drive Options A B C D E F Vertical Airflow J07NC J10NC J10ND J15NC J15ND J20NC J20ND Std. Mtr. and Drv. High Static Mtr. and Drv. Std. Mtr. and Drv. High Static Mtr. and Drv. Std. Mtr. and Drv. High Static Mtr. and Drv. Std. Mtr. and Drv. High Static Mtr. and Drv. Std. Mtr. and Drv.
505429-JTG-F-1010 Corner Weights & Center of Gravity J25NC Unit Evaporator Section Drive HP Cabinet Wt (lb) Model Blower Drive Weight Center of Section Section (lbs.) Gravity Cabinet Cabinet Ship Opera CG X CG Y Wt (lb) Wt (lb) ping ting 4 Point Load Location (lbs.) A B C D 6 Point Load Location (lbs.) A B C D E F Vertical Airflow 5 7.5 J25NC 539 539 463 463 111 138 1067 1130 1067 1157 19.0 19.3 45.5 45.
505429-JTG-F-1010 TOP VIEW Ø 1.72 KNOCKOUT ELECTRIC HEAT Ø 1.718 KNOCKOUT FOR ELECTRIC HEAT 20.31 20.313 8.84 8.837 9.25 9.246 13.44 15.920 8.22 5.135 17.59 15.63 14.590 18.628 TOP VIEW - BLOWER OUTLET J10NC/ND INDOOR TOP VIEW - BLOWER OUTLET J07NC INDOOR FRONT AND SIDE VIEW Ø 1.718 KNOCKOUT POWER ACCESS 3.66 4.56 7.06 Ø 0.875 KNOCKOUT POWER ACCESS 65.000 6.38 FIELD PIPING CONNECTIONS 35.000 SYSTEM 2 20.531 17.85 15.50 SYSTEM 1 13.13 10.73 2.000 52.000 56.
505429-JTG-F-1010 HORIZONTAL CONFIGURATION 30.00 35.00 30.00 60.
505429-JTG-F-1010 TOP VIEW Ø 1.718 KNOCKOUT FOR ELECTRIC HEAT 23.85 10.00 10.50 18.84 3.79 26.34 21.82 TOP VIEW - BLOWER OUTLET J15NC/ND INDOOR FRONT AND SIDE VIEW 3.66 4.56 7.06 1-1/4” CONDUIT KNOCKOUT Ø 1.718 POWER ACCESS 1/2” CONDUIT KNOCKOUT Ø 0.875 CONTROLS ACCESS 75.00 6.44 FIELD PIPING CONNECTIONS 42.00 27.53 SYSTEM 2 17.85 15.50 13.13 SYSTEM 1 10.73 2.00 70.50 74.50 FRONT VIEW - RETURN AIR J15NC/ND INDOOR 2.00 DRAIN 3/4” ABS PIPE CONNECTION 7.12 1.88 33.
505429-JTG-F-1010 HORIZONTAL CONFIGURATION 33.000 42.000 33.000 66.
505429-JTG-F-1010 TOP VIEW 1-1/4” CONDUIT KNOCKOUT (Ø 1.718) ELECTRIC HEAT CONTROL WIRE CONNECTION 1-1/4” CONDUIT KNOCKOUT (Ø 1.718) ELECTRIC HEAT POWER CONNECTION 22.86 8.83 9.25 15.90 BLOWER OPENING 9.25 5.14 4.14 1-1/4” CONDUIT KNOCKOUT (Ø 1.718) ELECTRIC HEAT CONTROL WIRE CONNECTION 25.30 1-1/4” CONDUIT KNOCKOUT (Ø 1.718) ELECTRIC HEAT POWER CONNECTION 18.63 BLOWER OPENING 18.63 BLOWER OPENING 54.57 75.64 TOP VIEW BLOWER OUTLET J20NC/ND INDOOR FRONT AND SIDE VIEW 3.66 4.56 7.
505429-JTG-F-1010 HORIZONTAL CONFIGURATION 30.00 35.00 30.00 60.
505429-JTG-F-1010 TOP VIEW 22.03 62.37 22.49 5.31 22.02 5.31 2.58 9.05 3.00 19.03 4X Ø.88 K0 CONTROLS CONNECTION 15.92 Ø 0.88 K0 ELECTRIC HEAT CONNECTION 57.69 FRONT AND SIDE VIEW 36.69 74.59 Ø 1.38 KO Ø 0.88 LIQUID CONNECTION 37.28 33.22 Ø 2.13 SUCTION CONNECTION Ø 1.38 KO 24.98 Ø 0.88 DRAIN CONNECTION 7.64 3.53 2.36 46.97 3.37 4.08 4.22 0.63 95.59 100.13 FRONT (RETURN AIR) VIEW 38.
505429-JTG-F-1010 HORIZONTAL CONFIGURATION RETURN AIR SUPPLY AIR 73.3 74.
505429-JTG-F-1010 PIPING, ELECTRICAL AND DUCT OPENING CONNECTION SIZES MODEL J07NC J10NC J10ND J15NC J15ND J20NC J20ND J25NC SYSTEM DATA No. Refrigeration Circuits Suction Line OD (in.) Liquid Line OD (in.
505429-JTG-F-1010 Unit Mounting - J07 Thru 20NC/ND The split air handling units can be applied in various horizontal positions. The Typical Suspension of AHU’s From Ceiling Figure shows recommended suspension rigging using properly sized all-thread and metal c-channel. All components to suspend an AHU must be field supplied. Please refer to the units total weight, center of gravity and corner weights. (Horizontal position) shown in the appropriate table for proper support sizing.
505429-JTG-F-1010 Unit Mounting - J25NC channels and hardware. The channels extend across the evaporator coil section, the heating coil section (if included) and the blower section. Each channel is to be bolted to each section as shown. The J25NC evaporator blower may be suspended from the joists with isolation type hangers or hooks. Suspension accessories 1HH0403 (J25NC) may be ordered separately.
505429-JTG-F-1010 NOTE: Do not use a heat pump thermostat. R C Y1 G W1 W2 THERMOSTAT SINGLE STAGE COOLING TWO STAGE HEATING NOTE: Liquid line solenoid is not included or required on 7.5 Ton Single Stage Units.
505429-JTG-F-1010 NOTE: Do not use a heat pump thermostat. R C Y1 G Y2 W1 W2 THERMOSTAT TWO STAGE COOLING TWO STAGE HEATING NOTE: Liquid line solenoid is only activated during second stage cooling operation.
505429-JTG-F-1010 R C Y1 G Y2 W1 W2 NOTE: Do not use a heat pump thermostat. THERMOSTAT TWO STAGE COOLING TWO STAGE HEATING NOTE: Liquid line solenoid is not included or required on any 4 pipe units.
505429-JTG-F-1010 W1 W2 G C Y1 X R THERMOSTAT SINGLE STAGE COOLING TWO STAGE HEATING NOTE: Liquid line solenoid is not included or required on 7.5 Ton Single Stage Units. Typical Field Wiring Diagram - J07NC Evaporator Unit with J07YC Condenser Unit NOTE: On non J**NC/ND Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit.
505429-JTG-F-1010 W1 W2 G C Y1 Y2 X R THERMOSTAT TWO STAGE COOLING TWO STAGE HEATING NOTE: Liquid line solenoid is only activated during second stage cooling operation. Typical Field Wiring Diagram - J10 thru 20NC Evaporator Unit with J10 thru 20YC Condenser Unit NOTE: On non J**NC/ND Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit.
505429-JTG-F-1010 Typical Field Wiring Diagram - J25NC Evaporator Unit with J25YC Condenser Unit NOTE: On non J**NC/ND Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit.
505429-JTG-F-1010 W1 W2 G C X Y1 Y2 R THERMOSTAT TWO STAGE COOLING TWO STAGE HEATING NOTE: Liquid line solenoid is not included or required on any 4 pipe units. Typical Field Wiring Diagram - J10 thru 20ND Evaporator Unit with J10 thru 20YD Condenser Unit NOTE: On non J**NC/ND Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit.
505429-JTG-F-1010 Y1 R C G X W1 W2 THERMOSTAT SINGLE STAGE COOLING TWO STAGE HEATING Y1 R C G X W1 W2 THERMOSTAT SINGLE STAGE COOLING TWO STAGE HEATING Typical Field Wiring Diagram - Twin J10 thru 20NC Evaporator Units with 4-Pipe Condenser Unit NOTE: On non J**NC/ND Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit.
505429-JTG-F-1010 Y1 Y2 G X C R W1 THERMOSTAT TWO STAGE COOLING SINGLE STAGE HEATING THERMOSTAT TWO STAGE COOLING SINGLE STAGE HEATING Y1 Y2 G X C R W1 Typical Field Wiring Diagram - Single 4-Pipe Evaporator Unit with Twin Condenser Units NOTE: On non J**NC/ND Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit.
Y1 R C G X W1 W2 Y1 R C G X W1 W2 THERMOSTAT SINGLE STAGE COOLING TWO STAGE HEATING THERMOSTAT SINGLE STAGE COOLING TWO STAGE HEATING Typical Field Wiring Diagram - Twin J07NC Evaporator Units with 4-Pipe Condenser Unit NOTE: On non J**NC/ND Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit. Subject to change without notice. Printed in U.S.A. Copyright © 2010 by Johnson Controls, Inc. All rights reserved.