Product Overview

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc.
www.johnsoncontrols.com
1
Code No. LIT-1900655
Issued July 8, 2015
Description
The HE-6800 Series Humidity Transmitters with Temperature Sensor
provide both humidity and temperature sensing in room wall-mount
applications. The transmitter offers local warmer/cooler temperature
setpoint adjustment and temporary occupancy override. The humidity
sensor provides Relative Humidity (RH) accuracy of ±2% or ±3% RH
and measures RH over the entire range of 0 to 100%.
A warmer/cooler dial is included on certain models for minor
temperature adjustments from the setpoint. All models feature an
occupancy override button that allows the user to override time-of-day
scheduling when the space is occupied outside of the normal occupied
hours schedule. The transmitter also includes DIP switches to enable
or disable override and Light-Emitting Diode (LED) functions. In
addition, all models feature a user-selectable 0 to 5 VDC or
0 to 10 VDC humidity output switch, and a power supply selection
switch.
The HE-6800 Series Humidity Transmitters include screw terminal
block terminations that provide flexibility for field wiring. All models
include a 6-pin modular jack access port for connecting accessories to
the Zone Bus. This feature allows a technician to commission or
service the controller via the transmitter.
Features
controller configuration DIP switch — allows users to adjust the
room comfort and choose occupancy features that match the
application and transmitter
power supply selection switch — enables transmitter use in high
input voltage applications
user-selectable humidity output — provides either a 0 to 5 VDC or
0 to 10 VDC output for compatibility with various controllers
occupancy Light-Emitting Diode (LED) indicator — displays the
current operating mode of the controller (VMA12 and VMA14 Series
only)
manual override pushbutton (PB) — overrides time-of-day
scheduling when the space is occupied outside of the normal
occupied hours schedule
warmer/cooler setpoint dial (select models) — allows for minor
temperature adjustments from the setpoint
Repair Information
If the HE-6800 Series Humidity Transmitter fails to operate within its
specifications, replace the unit. For a replacement transmitter, contact
the nearest Johnson Controls® representative.
Selection Charts
HE-6800 Series Humidity Transmitter with Temperature Sensor Product Code Numbers
Product Code Number Temperature Sensing
Element
Humidity Accuracy
(% RH)
Warmer/Cooler Temperature
Setpoint Adjustment Override
Enclosure
Dimensions (mm)
HE-68N2-0N00WS Nickel ±2% No 80 x 80
HE-68N3-0N00WS Nickel ±3% No 80 x 80
HE-68N2-1N00WS Nickel ±2% Yes 80 x 80
HE-68N3-1N00WS Nickel ±3% Yes 80 x 80
HE-68P2-0N00WS Platinum ±2% No 80 x 80
HE-68P3-0N00WS Platinum ±3% No 80 x 80
HE-68P2-1N00WS Platinum ±2% Yes 80 x 80
HE-68P3-1N00WS Platinum ±3% Yes 80 x 80
HE-6863-0N00WS 10,000 Thermistor ±3% No 80 x 80
HE-6863-1N00WS 10,000 Thermistor ±3% Yes 80 x 80
Optional Accessories
Product Code Number Description
ACC-INSL-0
1
1. These foam pads help prevent drafts from entering the unit through the wall, and make installation easier when mounting on an uneven surface.
Wallbox Mounting Pad (10 per Bag)
ACC-INSL-1
1
Surface Mounting Pad (10 per Bag)
NS-WALLPLATE-0 Adapts an HE-6800 Series Humidity Transmitter (3-3/16 x 3-3/16 in. [80 x 80 mm]) to a Standard
3-3/16 x 4-3/4 in.
(80 x 120 mm) Wallbox
T-4000-119 Allen-Head Adjustment Tool (30 per Bag)
HE-6800 Series Humidity Transmitters with Temperature Sensor
HE-6800 Series Humidity Transmitters with Temperature Sensor