Install Instructions
Table Of Contents
HE-6800 Series Humidity Transmitters with Temperature Sensor Installation Instructions4
Setup and Adjustments
Controller Configuration DIP Switch and
LED Mode
A DIP switch configures the HE-6800 for use with the
desired controller by enabling or disabling the manual
override PB and the LED. To change the controller
mode, use the three position DIP switch located on the
PCB. See Figure 4 and consult Table 2 to determine
the controller compatibility.
For all transmitter models, the factory default
LED mode is LED Mode:ON. The DIP switch positions
enable/disable the functions listed in Table 3.
Table 1: Terminal Block Wiring
Terminal Signal Designation
1 Temperature Sensor and Manual Override
2 Temperature Sensor Common
3 Setpoint Common and LED Common
4 Setpoint
5
24 VAC (+15 VDC – VMA Only
1
)
6 Common (for Power, RH Output, Zone
Bus, or Manual Override)
7 Zone Bus
8 LED and Manual Override
9 RH Output (0 to 10 VDC)
1. The +15 VDC power supply is used only when an
HE-6800 Series Humidity Transmitter is connected to
a VMA Controller.
!
CAUTION: Risk of Property Damage.
Do not use switch settings other than
those shown in Figure 4. Using other
switch settings may cause incorrect
controller operation or damage to the
element, controller, and controlled
equipment.
Figure 4: Controller Configuration
DIP Switch Positions
DIP switch in the
default position.
KEY:
Switch is in up position (ON)
Switch is in down position (OFF)
Note: Read switch positions
from left to right.
LED MODE
OFF
ON
NO
PB
NO
12
3
REMOVING THE CIRCUIT
BOARD VOIDS WARRANTY
FIG:dip_switch
Table 2: Controller Compatibility with LED Mode and PB
Types of
HE-6800
LED Mode
(Figure 4)
Features
Enabled on
HE-6800
Features Recognized by Controller
AHU UNT1100 VAV1xx or
UNT1xx
VMA12
Series
1
VMA14
Series
1
All Models
LED Off
2
Sensor and
Manual
Override
No Yes Yes Yes Yes
LED On Sensor,
Manual
Override, and
LED
No No No Yes Yes
No PB Room Sensor
Only
Yes Yes Yes Yes Yes
1. For these controllers, the LED appears brighter when pressing the manual override PB.
2. Holding the manual override PB for more than 2 seconds may affect the sensor reading.