Install Instructions

HE-6800 Series Humidity Transmitters with Temperature Sensor
Installation Instructions
1
Refer to the QuickLIT Web site for the most up-to-date version of this document.
Applications
The HE-6800 Series Humidity Transmitters with
Temperature Sensor provide both humidity and
temperature sensing in room wall-mount applications.
The transmitter offers local warmer/cooler temperature
setpoint adjustment and temporary occupancy
override. The humidity sensor provides Relative
Humidity (RH) accuracy of ±2% or ±3% RH and
measures RH over the entire range of 0 to 100%.
A warmer/cooler dial is included on certain models for
minor temperature adjustments from the setpoint. All
models feature an occupancy override button that
allows the user to override time-of-day scheduling
when the space is occupied outside of the normal
occupied hours schedule. The transmitter also includes
DIP switches to enable or disable override and
Light-Emitting Diode (LED) functions. In addition, all
models feature a user-selectable 0 to 5 VDC or
0 to 10 VDC humidity output switch, and a power
supply selection switch.
The HE-6800 Series Humidity Transmitters include
screw terminal block terminations that provide flexibility
for field wiring. All models include a 6-pin modular jack
access port for connecting accessories to the
Zone Bus. This feature allows a technician to
commission or service the controller via the transmitter.
Installation
Special Tools Needed
A 1/16 in. (1.5 mm) Allen wrench or a
Johnson Controls® T-4000-119 Allen-Head Adjustment
Tool is required during installation.
Accessories
Installing the HE-6800 Series Humidity Transmitter on
a wallbox requires accessory NS-WALLPLATE-0,
ordered separately.
Mounting
Location Considerations
Locate the HE-6800 Series Humidity Transmitter:
on a partitioning interior wall, and approximately
5 ft (1.5 m) above the floor in a location of average
temperature
away from direct sunlight, radiant heat, outside
walls, behind doors, air discharge grills, stairwells,
or outside doors
away from steam or water pipes, warm air stacks,
unconditioned areas (no heating and no cooling),
or sources of electrical interference
Note: The HE-6800 Series Humidity Transmitter is
shock and vibration resistant; however, be careful not
to drop the unit or mount it where it could be exposed
to excessive vibration.
The following ambient operating conditions apply:
Temperature: 32 to 131°F (0 to 55°C)
Humidity: 10 to 95% RH, noncondensing;
86°F (30°C) maximum dew point
To mount the transmitter to the wall:
1. Use a 1/16 in. (1.5 mm) Allen wrench or
Johnson Controls T-4000-119 Allen-Head
Adjustment Tool to loosen the security screw on
the top of the unit.
IMPORTANT: Use the HE-6800 Series Humidity
Transmitter only to provide input to equipment under
normal operating conditions. Where failure or
malfunction of the transmitter could lead to personal
injury or property damage to the controlled
equipment or other property, additional precautions
must be designed into the control system.
Incorporate and maintain other devices, such as
supervisory or alarm systems or safety or limit
controls, intended to warn of or protect against
failure or malfunction of the transmitter.
HE-6800 Series Humidity Transmitters with
Temperature Sensor
Installation Instructions
HE-68xx-xN00WS
Part No. 24-10409-28, Rev. B
Issued April 12, 2011
Supersedes October 1, 2010