Product Overview
Table Of Contents
Figure 3: FCP Thermostat dimensions, in. (mm)
Features and benefits
• Compatible with 2-pipe and 4-pipe FCU with up to a
3- speed fan, conventional PTAC, and heat pump PTAC
with or without auxiliary heat
• Pre-installed lead wires for fast installation
• Pre-set installer and user configurations—Configure
your thermostat easily with 20 pre-set installations
• Configurable normally open (NO)/normally closed (NC)
contact to set the occupied or unoccupied mode
• Onboard and remote temperature sensor available
• White LED backlight—Adjustable brightness for easy
operation in the dark
• FCP-PA-701 features up to six programmable periods
per day
• FCP-PA-701 features battery backup—RTC backup with
a minimum backup time of 48 hours
• Temperature in °F or °C
Applications
The FCP Thermostat is compatible with most 24 VAC FCU
or PTAC applications.
The following list shows the compatible configurations of
the equipment:
• 2-Pipe with up to a 3-speed fan
• 4-Pipe with up to a 3-speed fan
• Conventional PTAC
• Heat pump PTAC with or without auxiliary heat
Ordering information
Table 2: FCP digital room thermostat for fan coil or
PTAC selection chart
Product code
number
Non-
programmable/
programmable
Backup
battery
for RTC
Johnson
Controls
logo
Color
FCP-NA-701-N Non-
programmable
No No White
FCP-NA-701-B Non-
programmable
No Yes White
FCP-PA-701-N 7-day
programmable
Yes No White
FCP-PA-701-B 7-day
programmable
Yes Yes White
The FCP Thermostat ships from the factory with a Quick
Start Guide, four mounting screws, one lock screw, seven
pre- installed terminal wires, and one wire label. The
FCP- PA- 701 also includes one coin cell battery.
Technical specifications
Table 3: FCP non-programmable and programmable
FCU or PTAC Thermostats technical specifications
Specification Description
Models Non-programmable: FCP-NA-701-N, FCP-NA-701-B
Programmable: FCP-PA-701-N, FCP-PA-701-B
Power requirements 20 VAC to 30 VAC, 60 Hz, max. 3 A (3 VA at 24 V nominal)
Output rating Valve and fan
outputs
1 A maximum per each relay channel
(Max. relays ON combination: 3 relays), 20 VAC to 30 VAC
Remote
sensor
10K ohm at 77°F (25°C) NTC sensor
Pipe sensor 10K ohm at 77°F (25°C) NTC sensor
Analog inputs
Set back NC/NO dry contact switch
Local temperature sensor
type
NTC temperature sensor, accurate to ±1°F (±0.6°C) at 77°F
(25°C)
Remote temperature sensor
type
NTC temperature sensor, accurate to ±2°F (±1.2°C) at 70°F
(21°C)
Wire size 18 AWG (100 ft [30.5 m] maximum) to 24 AWG (36 ft
[11 m] maximum)
Heat mode 45°F to 90°F (7°C to 32°C)Temperature
adjustment
range
Cool mode 60°F to 95°F (15°C to 35°C)
Local
temperature
sensor
±1°F (±0.6°C)
Remote
temperature
sensor
±2°F (±1.2°C) at 70°F (21°C)
Accuracy
Remote pipe
sensor
±5°F (±3.0°C)
Deadband 2°F to 5°F (1°C to 3°C)
Operating 14°F to 122°F (-10°C to 50°C); 5% RH to 90% RH,
noncondensing
Ambient
conditions
Storage -4°F to 140°F (-20°C to 60°C); 5% RH to 90% RH,
noncondensing
Disconnection means Type 1B
Pollution degree 2
Rated impulse voltage 330 V
Automatic Action 100,000 cycles
Ratings for supply and
loading
20 VAC to 30 VAC
Dimensions H x W x D 3.27 in. x 3.94 in. x 0.98 in. (83 mm x 100 mm x 25 mm)
Shipping weight Product with packing and accessories: 10.1 oz (285 g)
Thermostat only: 4.9 oz (138 g)
Trim plate: 1.2 oz (33 g)
Compliance ETL/cETL Listed, Mexico NOM
Conforms to UL STD. 60730-1 & 60730-2-9
Certified to CSA STD. E60730-1 & E60730-2-9
The performance specifications are nominal and conform to
acceptable industry standards. For application at conditions
beyond these specifications, consult the local Johnson
Controls office. Johnson Controls shall not be liable for
damages resulting from misapplication or misuse of its
products.
Repair information
If the FCP Thermostat fails to operate within its
specifications, replace the unit. For a replacement
FCP Non-Programmable and Progammable Fan Coil or PTAC Thermostat Product Bulletin2