F261 Series Flow Switches Installation Instructions
6
Wiring
The F261 models have three color-coded terminals.
Red is common. See Figure 11 and Table 3 for switch
action.
Setup and Adjustments
!
WARNING: Risk of Electric Shock.
Disconnect the power supply before
making electrical connections. The
printed circuit board and its components
are at AC line voltage. Contact with
components carrying hazardous voltage
can cause electric shock and may result
in personal injury or death.
AVERTISSEMENT : Risque de
décharge électrique.
Débrancher l'alimentation avant de
réaliser tout raccordement électrique.
Le circuit imprimé et ses composants
présentent une tension CA. Tout contact
avec des composants porteurs de
tensions dangereuses risque d'entraîner
une décharge électrique et de provoquer
des blessures graves, voire mortelles.
IMPORTANT: Use the terminal screws provided
(M4 x 8 crosshead). Substitution of other screws
voids the warranty and agency approvals.
IMPORTANT: To prevent moisture from entering
and condensate from forming inside the
Type 3R/IP43 enclosure, do not block the drain hole
provided.
To prevent moisture from entering and condensate
from forming inside the Type 4/IP67 enclosure, do
not remove the case-to-cover O-ring provided on
the flow switch.
IMPORTANT: Use copper conductors only. Make
all wiring in accordance with local, national, and
regional regulations.
IMPORTANT: Do not exceed the control’s electrical
ratings. Exceeding the control’s electrical ratings can
result in permanent damage to the control and void
any warranty.
Table 3: F261 Control Switch Action
Flow Action Switch Closure
Increase Red to Yellow
Decrease Red to Blue
!
CAUTION: Risk of Property Damage.
Do not set the switch lower than the
factory setting. The switch is factory set
at approximately the minimum flow rate.
A lower setting may result in the switch
failing to return to a no-flow position
which may result in damage to the
controlled equipment or other property.
MISE EN GARDE : Risque de dégâts
matériels.
Ne pas régler le commutateur sur une
valeur inférieure au paramètre d'usine.
Le commutateur est réglé en usine sur
une valeur correspondant environ au
débit minimum. Un réglage sur une
valeur inférieure risque d'empêcher le
commutateur de revenir sur une position
« aucun-débit », ce qui risque
d'endommager l'équipement contrôlé ou
de provoquer d'autres dégâts matériels.
Figure 11: F261 Control Switch Action
Red
Yell ow
Blue
+
-