Product Overview
Table Of Contents
FANs 216, 1628.3
Product/Technical Bulletin EP-8000
Issue Date 1196
© 1996 Johnson Controls, Inc.
1
Part No. 24-85368-36, Rev. E
Code No. LIT-216370
EP-8000 Series Electro-Pneumatic Transducers
convert a voltage or current signal from an electronic
controller into a pneumatic output pressure signal. An
increase or decrease in the input signal proportionally
increases or decreases (respectively) the output
pressure signal from the EP-8000. Four models are
available, which are grouped into two basic versions:
low-volume output units (non-relay) and high-volume
output units (relay).
Electro-Pneumatic
Transducer EP-8000-1
Low Volume Output
Input
0 to 1 0 VDC
Output
1 to 18 psi
g
Test Port
Ze ro Ad
j
.
Electro-Pneumatic
Transducer EP-8000-4
Hi
g
h Volume Output
Inpu t
4 to 20 ADC
Output
3 to 15 psi
g
Test Port
Zero Ad
j
.
Figure 1: The EP-8000 Low Volume (Left) and the
EP-8000 High Volume (Right)
Features and Benefits
❑
Compact, Simple Design
Eases installation on a variety of mounting
surfaces, including direct mounting on pneumatic
valve actuators
❑
Choice of 0-10 VDC or
4-20 mA Input Range
Interfaces with a wide range of controllers, making
the unit ideal for retrofit installations
❑
Hypodermic Needle Test
Point
Allows for fast and easy output pressure signal
measurement
❑
Factory Set,
Fully
Adjustable Zero and Span
Facilitates field calibration, saving installation costs
❑
High Accuracy with Low
Hysteresis
Provides many years of use with less time spent on
maintenance
EP-8000 Series Electro-Pneumatic Transducers