Install Instructions

Published in U.S.A. www.johnsoncontrols.com
CSD Series Current Devices—Split Core Installation Instructions 5
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Technical Specifications
Split Core Models CSD-CF0A0-1, CSD-CFOJO-1, and CSD-CA1G0-1
Product Code CSD-CF0A0-1 CSD-CF0J0-1 CSD-CA1G0-1
Amperage Range 0.15–200 A 1.5–200 A 1.25–135 A
Switch Setpoint Fixed Fixed Adjustable
Output Relay No
Actuation Coil No
Switch LED Indication No No Yes
Relay LED Indication No
Trip Setpoint Value 0.15 A 1.5 A 1.25-135 A
Current Switching Mode Under Current Sensing Under Current Sensing Over/Under Current
Sensing
Sensor Supply Voltage Induced from power conductor cable.
Wire Size 2.1–0.6 mm (12–22 AWG) Diameter Recommended
Status Output Switch Normally Open.
Switch Load Capacity 1 A at 30 VAC/42 VDC Maximum
Isolation Voltage 600 VAC rms
Temperature Range -15 to 60°C (5 to 140°F)
Frequency Range 50/60 Hz
Humidity Range 0–95% Noncondensing
Screw Torque 0.5 N·m (4 lb·in.)
Dimension 69 x 65 x 27 mm (2-23/32 x 2-9/16 x 1-1/16 in.)
Aperture (Sensing Hole) Size 18 x 20 mm Diameter (0.72 x 0.78 in. Diameter)
Compliance United States UL Listed, File E310692, CCN NRNT, Under UL 508, Industrial Control Equipment
Canada UL Listed, File E310692, CCN NRNT7, Under CAN/CSA C22.2 No. 14-M91
Industrial Control Equipment
Europe CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the
essential requirements and other relevant provisions of the EMC Directive and the Low
Voltage Directive.
Shipping Weight 0.16 kg (0.35 lb)
The performance specifications are nominal and conform to acceptable industry standards. For application of conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS
WESTENDHOF 3
45143 ESSEN
GERMANY
JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA
JOHNSON CONTROLS
C/O CONTROLS PRODUCT
MANAGEMENT
NO. 22 BLOCK D NEW DISTRICT
WUXI JIANGSU PROVINCE 214142
CHINA