System 450™ Series Modular Controls Product Bulletin 19
Analog Output Voltage Mode (0–10 VDC):
10 VDC maximum output voltage
10 mA maximum output current
Requires an external load of 1,000 ohm or more
The AO operates in Voltage Mode when connected to devices with impedance greater
than 1,000 ohm. Devices that drop below 1,000 ohm may not operate as intended with
Voltage Mode applications.
Current Mode (4–20 mA):
Requires an external load between 0–300 ohm
The AO operates in Current Mode when connected to devices with impedances less
than 300 ohm. Devices that rise above 300 ohm may not operate as intended with
Current Mode applications.
Analog Input Accuracy Resolution: 14 bit
Control Construction Independently mounted control, surface mounted with Lexan® 950 enclosure suitable
for DIN rail mounting or direct mounting to a hard, even surface.
Dimensions (H x W x D) 127 x 61 x 61 mm (5 x 2-3/8 x 2-3/8 in.)
Weight C450CPN-x: 195 g (0.43 lb)
C450CPW-100: 195 g (0.43 lb)
C450CQN-x: 195 g (0.43 lb)
Compliance North America: cULus Listed; UL 60730, File E27734, Vol. 1; FCC Compliant to
CFR47, Part 15, Subpart B, Class B
Industry Canada (IC) Compliant to Canadian ICES-003, Class B limits
Europe: CE Mark - Johnson Controls Inc., declares that this product is in compliance
with the essential requirements and other relevant provisions of the Low Voltage
Directive (2006/95/EC); EMC Directive (2004/108/EC); RoHS Directive (2002/95/EC);
WEEE Directive (2002/96/EC).
Australia: Mark: C-Tick Compliant (N1813)
C450CxN Control Modules with Relay Output (Part 1 of 2)
Product C450Cxx: System 450 Control Module models are sensing controls and operating
controls with LCD, four-button touchpad, and On/Off relay output
C450CBN-x: Control Module with one SPDT output relay
C450CCN-x: Control Module with two SPDT output relays
Supply Power C450YNN-1 Power Supply Module or
24 (20-30) VAC Safety Extra-Low Voltage (SELV) (Europe) or Class 2 (North America)
50/60 Hz, 10 VA minimum
Ambient Operating Conditions Temperature: -40 to 66°C (-40 to 150°F) when using 0–10 VDC outputs;
-40 to 40°C (-40 to 104°F) when using 4–20 mA outputs
Humidity: Up to 95% RH noncondensing; Maximum Dew Point 29°C (85°F)
Ambient Shipping and Storage
Conditions
Temperature: -40 to 80°C (-40 to 176°F)
Humidity: Up to 95% RH noncondensing; Maximum Dew Point 29°C (85°F)
Input Signal 0–5 VDC, 1,035 ohm at 25°C (77°F) for an A99 PTC Temperature Sensor
Output Relay Contacts General: 1/2 HP at 120/240 VAC, SPDT
Specific: AC Motor Ratings 120 VAC 208/240 VAC
AC Full-load Amperes: 9.8 A 4.9 A
AC Locked-Rotor Amperes: 58.8 A 29.4 A
_____________________________________
10 Amperes AC Non-inductive at 24/240 VAC
Pilot Duty: 125 VA at 24/240 VAC
Analog Input Accuracy Resolution: 14 bit
C450Cxx Control Modules with Analog Output (Part 2 of 2)