System 450™ Series Modular Controls Product Bulletin18
Technical Specifications
P499RAP-107C Electronic Pressure Transducer: 0 to 750 psig; 1/8 in.-27 NPT External Thread (Style 49)
Order WHA-PKD3 type wire harness separately.
P499RAP-107K Electronic Pressure Transducer Kit: 0 to 750 psig; 1/8 in.-27 NPT External Thread (Style 49)
WHA-PKD3-200C wire harness included.
P499RAPS102C Electronic Pressure Transducer: 0 to 200 psis (sealed for wet and freeze/thaw applications);
1/8 in.-27 NPT External Thread (Style 49). Order WHA-PKD3 type wire harness separately.
P499RAPS102K Electronic Pressure Transducer Kit: 0 to 200 psis (sealed for wet and freeze/thaw applications);
1/8 in.-27 NPT External Thread (Style 49). WHA-PKD3-200C wire harness included.
P499RCP-107C Electronic Pressure Transducer: 0 to 750 psig; 1/4 in. SAE 45° Flare Internal Thread
(7/16-20 UNF) with Depressor (Style 47). Order WHA-PKD3 type wire harness separately.
P499RCP-107K Electronic Pressure Transducer Kit: 0 to 750 psig; 1/4 in. SAE 45° Flare Internal Thread
(7/16-20 UNF) with Depressor (Style 47). WHA-PKD3-200C wire harness included.
WHA-PKD3-200C Plug and 3-Wire Harness for P499 Electronic Pressure Transducers: 2.0 m (6-1/2 ft) cable
WHA-PKD3-400C Plug and 3-Wire Harness for P499 Electronic Pressure Transducers: 4.0 m (13 ft) cable
WHA-PKD3-600C Plug and 3-Wire Harness for P499 Electronic Pressure Transducers: 6.0 m (19-5/8 ft) cable
1. Refer to the P499 Series Electronic Pressure Transducers Product/Technical Bulletin (LIT-12011190) on the
Johnson Controls Product Literature Web site for more information.
Table 9: System 450 Compatible P499 Series Electronic Pressure Transducer and WHA-PKD3 Wire
Harness Ordering Information
1
(Part 2 of 2)
Product Code
Number
Product Description
C450Cxx Control Modules with Analog Output (Part 1 of 2)
Product C450Cxx: System 450 Control Module models are sensing controls and operating
controls with LCD, four-button touchpad, and analog output
C450CPN-x: Control Module with one analog output
C450CPW-100: Control Module with Hybrid Analog Output and High Input Signal
Selection
C450CQN-x: Control Module with two analog outputs
Supply Power C450YNN-1 Power Supply Module or
24 (20–30) VAC Safety Extra-Low Voltage (SELV) (Europe) or Class 2 (North America)
50/60 Hz, 10 VA minimum
Ambient Operating Conditions Temperature: -40 to 66°C (-40 to 150°F) when using 0–10 VDC outputs;
-40 to 40°C (-40 to 104°F) when using 4–20 mA outputs
Humidity: Up to 95% RH noncondensing; Maximum Dew Point 29°C (85°F)
Ambient Shipping and Storage
Conditions
Temperature: -40 to 80°C (-40 to 176°F)
Humidity: Up to 95% RH noncondensing; Maximum Dew Point 29°C (85°F)
Input Signal 0–5 VDC; 1,035 ohm at 25°C (77°F) for an A99 PTC Temperature Sensor