Product Overview

System 450™ Series Modular Controls Product Bulletin12
Hybrid Analog Output and High Input Signal
Selection Control
Figure 14 shows a System 450 control system that
uses the hybrid analog output to control motor speed
on an Electronically Commutated (EC) condenser fan
motor and the High Input Signal Selection feature to
provide the pressure input signal according to the
higher of the two pressure values sensed at the two
transducers.
FIG:C450CPW-100_app_anlg_exmpl
L1 L2
Analog Output
Signal
L1
L2
COM
A
O1
Active/Passive Sensor DIP Switches
DIP Switch 1 and 2 are OFF; switch 3 is ON.
Electronically Commutated
(EC) Motor Speed Control
Input Circuit
Figure 14: System 450 EC Motor Speed Control Application Using High Input Signal Selection