R-75
MS Series Temperature Stage Control Modules (Continued)
Multi-Stage Electronic Temperature Controls
MS4PM24T Panel Mount Control Wiring
ms4pm24t.eps
SC
S2
S1
D
V1 V2
Internal to Control
1234
C
Stage
3
Stage
2
Stage
1
Stage
4
Common
Power
Supply
Binary
Input
Binary/Sensor
Common
Auxiliary Temperature Sensor
Process
Sensor
Refer to Ratings T
able for more information
MS4DR24T Din Rail Mount Control Wiring
ms4dr24t.eps
Internal to Control
Auxiliary
T
emperature
Sensor
Stage 3
Stage 4
Stage
1
Stage
CDD
S2
SC
Power Supply
1
C1
C4
C2
3
C3
V1
V2
Process
Sensor
Binary Input
Sensor Common
Binary and Sensor Common
Terminal Not Used
See Ratings Table
for more information
Technical Specifications
Note: Relay outputs must not exceed 20 Amperes total connected load. Open collector transistors on the MS1 Alarm Circuits have a maximum
rating of 40 VDC 100 mA. Alarms require separate power source.
MS Series Temperature Stage Control Modules
Power Requirements 24 VAC, 50/60 Hz, Class 2 (20 to 30 VAC)
Power Consumption 5 VA at 24 VAC
Accuracy 1.8°F ( 1°C)
Ambient Conditions Operating +14 to +140°F (-10 to +60°C); 0 to 95% RH (noncondensing)
Storage -22 to +176°F (-30 to +80°C); 0 to 95% RH (noncondensing)
Agency Listings UL Recognized: File E194024, CCN XAPX2
Canadian UL Recognized: File E194024, CCN XAPX8
Dimensions
(H x W x D)
Panel Mount 1.38 x 2.95 x 2.68 in. (35 x 75 x 68 mm)
DIN Rail 4.65 x 2.76 x 2.07 in. (118 x 70 x 53 mm)
Electrical Ratings
120 VAC 240 VAC 24 VDC
Horsepower 1/4 1/2 ---
Full Load Amperes 5.8 4.9 ---
Locked Rotor Amperes 34.8 29.4 ---
Inductive (Non-Motor)
Amperes
88 8
Pilot Duty VA 275 450 ---