Brochure

Table Of Contents
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc. www.johnsoncontrols.com
R-73
T46 Series Fan Coil Thermostat (Continued)
Multi-Stage Electromechanical Temperature Controls
Technical Specifications (Continued)
Operating Differentials
Note: The heavy line in each of the above figures is the nominal
operating temperature differential. Production thermostats may vary
from the norm, as indicated by the dotted line.
Electrical Ratings
Motor Ratings 120 V 208 V 240 V 277 V
T46 System and Fan Switches
AC Full Load A 12.0 6.9 6.0 5.2
AC Locked Rotor A 34.8 19.1 17.4 14.4
AC Non-Inductive A 6.5 6.5 6.5
Pilot Duty 125 VA, 24 to 277 VAC
T46 Thermostat Only
AC Full Load A 6.0 3.5 3.0
AC Locked Rotor A 34.8 19.1 17.4
AC Non-Inductive A 6.5 6.5 6.5
Pilot Duty 125 VA, 24 to 277 VAC
5
4
3
2
1
0
02468
2.2
1.1
Operating Differential F
0
Operating Differential C
0
Amperage Load
T46A, T46S Heating
Operating Differential for T46A and Heating Side of T46S
t46heat.eps
5
4
3
2
1
0
02468
2.2
1.1
Operating Differential F
0
Operating Differential C
0
Amperage Load
T46J, T46S Cooling
Operating Differential for T46J and Cooling Side of T46S
t46cool.eps
Typical Wiring Application for Heating
Typical Wiring Application for Cooling
Typical Wiring Application for Combination
Grey
Black
L1 (Hot)
Neutral
Orange
Red
To Fan
To Heating
T46ABH Auto-Off-Fan Selector Switch
with Continuous Fan (Heating Only)
t46auht.eps
Grey
Black
L1 (Hot)
Neutral
Orange
Blue
To Fan
To Cooling
T46JBH Auto-Off-Fan Selector Switch
with Continuous Fan (Cooling Only)
t46auco.eps
Black
L1 (Hot)
Neutral
Orange
To Fan
Changeover
Control
Grey
Valve
Red
Blue
B
R
Y
Fan
Off
T46SDH Off-Auto Selector Switch.
Used on Fan-Coil Unit with Cycling Valve and Continuous Fan.
Terminal Markings Shown for
A19CAC Changeover Control (Heating and Cooling)
t46_2.eps