Brochure

Table Of Contents
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc. www.johnsoncontrols.com
R-69
Typical Wiring Diagram and Electrical Ratings for Line Voltage
Thermostats
Technical Specifications
T22SFB, T22TFB
Heating
System
Cooling
System
H
G
3
Heat Cool Heat Cool
Off Off
h
21
t22sfb.eps
Typical Wiring Diagram for Line Voltage Thermostat
Note: T25A Non-Inductive Ratings are 10.0, 9.2, 8.0 and 7.2 A.
T26A, T26S Non-Inductive Rating is 10.0 A,
120 to 277 VAC.
Electrical Ratings T22A, T22J, T22S, T25A, T26A, T26J, T26S
Motor Ratings VAC 120 208 240 277
AC Full Load A 6.0 3.4 3.0
AC Locked Rotor A 36.0 21 18.0
AC Non-Inductive A (1) (1) (1) (1)
Pilot Duty 125 VA, 24 to 277 VAC
Electrical Ratings T22BBC
Motor Ratings VAC 120 208 240
AC Full Load A 10.0 6.9 6.0
AC Locked Rotor A 60.0 41.4 36.0
Pilot Duty
125 VA, 24 to 277 VAC
Electrical Ratings T22CBC
1
, T26T
2
1. Heating rating only applies. Non-inductive ratings do not apply to Type T2CBC.
2. Non-inductive rating does not apply to the cooling side of T26T.
Motor Ratings VAC 120 208 240
Heat Cool Heat Cool Heat Cool
AC Full Load A 16.0 8.0 9.2 8.0 8.0 8.0
AC Locked Rotor A 96.0 48.0 55.2 48.0 48.0 48.0
Non-Inductive Rating 120 240 227
AC Non-Inductive A 22.0 22.0 22.0
Pilot Duty 125 VA, 120 to 240 VAC
Electrical Ratings T22TFB
Motor Ratings VAC 120 208 240
Heat Cool Heat Cool Heat Cool
AC Full Load A 16.0 8.0 9.2 8.0 8.0 8.0
AC Locked Rotor A 96.0 48.0 55.2 48.0 48.0 48.0
Pilot Duty 125 VA, 120 to 240 VAC
Multi-Stage Electromechanical Temperature Controls
Code No. LIT-1922600