R-64
A28PJ, A28PA Thermostat
A28 Two-Stage Agricultural Thermostat with NEMA 4X Enclosure
Description
The A28PJ and A28PA are two-stage
temperature controls with raintight and
dusttight enclosures.
Refer to the A28 Series Two-Stage
Temperature Controls with NEMA 1 Enclosure
Product Bulletin (LIT-125130) for important
product application information.
Features
rugged thermoplastic gasketed enclosures
that meet NEMA 4X specifications
O-ring sealed setpoint adjustment knobs
range scale with oversized white markings
for easy readability in low light
exposed portion of liquid-filled sensing
elements are plated and plastic coated to
resist damage in corrosive atmospheres
Applications
Designed for use in agricultural and industrial
applications that require compliance with
Article 547 of the National Electrical Code.
Repair Information
If the A28 Two-Stage Agricultural Thermostat
with NEMA 4X Enclosure fails to operate within
its specifications, replace the unit. For a
replacement thermostat, contact the nearest
Johnson
Controls®
representative.
Selection Chart
Technical Specifications
Product Code Number Switch Action Range °F (°C) Differential F° (C°) Bulb and Capillary Range Adjuster
A28PJ-1C Two-SPDT 30 to 110
(-1 to 43)
2 (1.1) each stage
2 to 7 (1.1 to 3.9) adjustable between stages
1-3/8 in. x 2-1/4 in.
coiled
Knob
A28PA-2C Two-SPDT 30 to 110
(-1 to 43)
2 (1.1) each stage
2 to 7 (1.1 to 3.9) adjustable between stages
1-3/8 in. x 2-1/4 in.
coiled
Knob
Electrical Ratings
Motor Ratings VAC 120 208 240 277
A28PJ
AC Full Load A 6.0 3.4 3.0
AC Locked Rotor A 36.0 20.4 18.0
Non-Inductive or Resistance Load A
(Not Lamp Loads)
10.0 9.2 8.0 7.2
Pilot Duty 125 VA, 24 to 277 VAC
1
1. When used as a two-circuit control, the total connected load must not exceed 2,000 VA.
A28PA
AC Full Load A 16.0 9.2 8.0
AC Locked Rotor A 96.0 55.2 48.0
Non-Inductive or Resistance Load A
(Not Lamp Loads)
16.0 9.2 8.0 7.2
Pilot Duty 125 VA, 24 to 277 VAC
1
Multi-Stage Electromechanical Temperature Controls
Code No. LIT-1927130