Brochure

Table Of Contents
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc. www.johnsoncontrols.com
R–55
A421 Series Electronic Temperature Controls with Integral Cycle Timer
(Continued)
Single-Stage Electronic Temperature Controls
Technical Specifications
A421 Series Electronic Temperature Controls
Power Consumption 1.8 VA maximum
Supply Power 24 VAC, 50/60 Hz, Class 2:
108/110/115/120 or 208/230/240 VAC, 50/60 Hz
Ambient Conditions Operating: -40 to 150°F (-40 to 66°C), 0 to 95% RH noncondensing
Shipping and Storage: -40 to 185°F (-40 to 85°C), 0 to 95% RH noncondensing
Temperature Control Range -40 to 212°F (-40 to 100°C) or -40 to 248ºF (-40 to 120ºC), depending on the model selected
Input Signal 1,035 ohms at 77F (25C) for A99 PTC temperature sensors
Sensor Offset Range ±5ºF or ±3ºC
Output Relay Contacts Electrical
Ratings
24 VAC Models:
100 VA, 30 VAC maximum, Class 2
120 VAC Model with Integral Power Cord:
Applied Voltage: 120 VAC
Full Load Amperes N.O. and N.C.: 12 A
Locked Rotor Amperes N.O. and N.C.: 72 A
Non-inductive Amperes N.O. and N.C.:12 A
Pilot Duty: 125 VA (N.O. contacts) at 24 to 120 VAC
120/240 VAC Models:
Applied Voltage: 120 VAC 208 VAC 240 VAC
Horsepower N.O. (N.C.) : 1 (0.25) hp 1 (0.33) hp 1 (0.5)
hp
Full Load Amperes N.O. (N.C.): 16 (5.8) A 9.2 (4.0) A 8.0 (4.9) A
Locked Rotor Amperes N.O. (N.C.): 96 (34.8) A 55.2 (24) A 48 (29.4) A
Non-inductive Amperes N.O. (N.C.):15 (10) A 10 (10) A 10 (10) A
Pilot Duty: 125 VA (N.O. contacts) at 24 to 240 VAC
125 VA (N.C. contacts) at 24 to 240 VAC
50 VA (N.C. contacts) at 24 VAC
Enclosure Material NEMA 1/IP20 high-impact thermoplastic or
NEMA 4X/IP66 watertight, corrosion-resistant, high-impact thermoplastic
Compliance North America: cULus Listed; UL 60730, File E27734, Vol. 1; FCC Compliant to CFR47, Part 15, Subpart B, Class B
Industry Canada (IC) Compliant to Canadian ICES-003, Class B limits
Europe: CE Mark – Johnson Controls, Inc. declares that this product is in compliance with the essential requirements and
other relevant provisions of the EMC Directive 2004/108/EC and the Low Voltage Directive 2006/95/EC.
Australia: Mark: C-Tick Compliant (N1813)