Brochure

Table Of Contents
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc. www.johnsoncontrols.com
R-41
A72 Series Two-Pole Heavy Duty Temperature Controls (Adjustable
Differential)
Description
The A72 Series Temperature Controls
incorporate a vapor charged sensing element
and heavy duty contacts.
Refer to the A70, A72 Series Temperature
Controls for Refrigeration and Heating
(LIT-125155) for important product application
information.
Line 2
Line1
M1
M2
A72 Series
Action on Increase
on Temperature
a27.eps
A72 Action Diagram
Features
The double-pole, single-throw (DPST) contact
block contains two isolated sets of contacts
that make or break simultaneously.
Applications
Use for automatic control of heavy electrical
loads.
Selection Charts
Technical Specifications
Product Code
Number
Switch
Action
Range
°F (°C)
Differential
F° (C°)
Bulb and
Capillary
Maximum Bulb
Temperature °F (°C)
Range
Adjuster
A72AA-1C DPST
Close high
Open low
-30 to 30
(-34 to -1)
4 to 25
(2 to 14)
3/8 in. x 3 in.
1
6 ft capillary
1. Packing nut assembly available for direct immersion applications, Code No. FTG13A-600R.
200
(93)
Screwdriver slot
A72AA-2C DPST
Close high
Open low
15 to 55
(-9 to 13)
3 to 30
(1.7 to 17)
3/8 in. x 3 in.
1
6 ft capillary
200
(93)
Screwdriver slot
A72AA-3C DPST
Close high
Open low
50 to 90
(10 to 32)
3 to 30
(1.7 to 17)
11/16 in. x 6-3/4 in.
Cross ambient
6 ft capillary
135
(57)
Screwdriver slot
A72AP-1C
2
2. Equipped with manual PUSH TO START button. Manual start feature is especially desirable on milk cooler jobs; permits manual start of the compressor when
bulb temperature is between closing and opening setting of switch.
DPST
Close high
Open low
-10 to 65
(-23 to 18)
4 to 40
(2 to 22)
11/16 in. x 6-3/4 in.
Cross ambient
6 ft capillary
130
(54)
Screwdriver slot
Replacement Covers
Product Code Number Description
CVR17A-620R Automatic reset cover
CVR17A-621R Manual reset cover
Electrical Ratings
Motor Ratings VAC 120
Single-Phase
208
1
Single-Phase
1. These full load and locked rotor ampere (not horsepower) ratings apply to hermetic compressors only.
240
1
Single-Phase
220
1
Two-Phase
208
Three-Phase
220
Three-Phase
Horsepower 233555
AC Full Load A 24.0 24.0 24.0 15.0 15.9 15.0
AC Locked Rotor A 144.0 144.0 144.0 90.0 95.4 90.0
AC Non-Inductive A 24.0 24.0 24.0
DC Non-Inductive A
2
2. This rating does not apply to the A72AP-1C Control.
3.0 0.5
Pilot Duty 125 VA, 120 to 600 VAC; 57.5 VA, 120 to 300 VDC
A72AA-3 Temperature Control
Single-Stage Electromechanical Temperature Controls
Code No. LIT-1927145