A25 Series Warm Air Limit Control with Manual Reset
Description
The A25 Warm Air Control Locks
out on a temperature increase to
the control setpoint. Manual reset
is required before the electrical
contacts can be reclosed.
The A25 Control is normally
located in a return air duct and is
wired to shut down air
conditioning or ventilating fans
when the temperature of the air
becomes excessively hot.
Refer to the A25 Series Warm Air
Control with Manual Reset
Product Bulletin (LIT-125118) for
important product application
information.
Applications
Use for high temperature cut-out.
A25 Series
Action on Increase
of Temperature
Y
B
R
a25.eps
A25 Series Action Diagram
Features
trip-free reset lever does not permit restarting until the reset lever is
manually released
the rod and tube type sensing element provides positive control
action
Repair Information
If the A25 Series Warm Air Limit Control with Manual Reset fails to
operate within its specifications, replace the unit. For a replacement
control, contact the nearest Johnson
Controls®
representative.
Selection Chart
Product Code
Number
Switch
Action
Range
°F (°C)
Range
Adjuster
Dial Stop
°F (°C)
A25AN-1C Single-Pole,
Single-Throw
(SPST),
Open high
25 to 215
(-4 to 102)
Knob High limit
set at 125 (52)
A25CN-1C Single-Pole,
Double-Throw
(SPDT)
25 to 215
(-4 to 102)
Knob High limit
set at 125 (52)
Factory Mutual Approved Models
A25AP-1C SPST
Open high
25 to 215
(-4 to 102)
Concealed
screwdriver slot
High limit
set at 125 (52)
A25CP-1C SPDT 25 to 215
(-4 to 102)
Concealed
screwdriver slot
High limit
set at 125 (52)
Technical Specifications
The maximum element temperature is 300°F (149°C).
Electrical Ratings
Motor Ratings VAC 120 208 240 277
AC Full Load A 16.0 9.2 8.0
AC Locked Rotor A 96.0 55.2 48.0
Non-Inductive A 16.0 A at 120/277 VAC
Pilot Duty 125 VA, 24 to 600 VAC
A25AP-1 Warm Air
Limit Control
A25AN-1 Warm Air
Limit Control
Single-Stage Electromechanical Temperature Controls