Brochure

Table Of Contents
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc. www.johnsoncontrols.com
R-32
A19 Series Fan or Cutout Control (Liquid Expansion Bulb)
Description
The A19 Series Fan or Cutout Control is a
wide range temperature control with
adjustable dial stops and mounting flange.
Refer to the A19E Series Warm Air Fan and
Duct Controls Low or Line Voltage Product
Bulletin (LIT-125075) for important product
application information.
Features
liquid charged element for fast response
may be mounted in any position
Applications
This control is designed for low or line voltage
applications including warm air or furnace fan
control.
Selection Chart
Technical Specifications
A19 Series Fan or Cutout Control (Liquid Expansion Bulb)
Product Code
Number
Application Switch
Action
Range
°F (°C)
Differential F° (C°) Adjustable Stop °F (°C) Bulb
Length
Maximum Bulb
Temperature °F (°C)
Min Max Min Max
A19EBA-1C Furnace Fan
Control
Close high
Single-Pole,
Single-Throw
(SPST)
50 to 250
(10 to 121)
9
(5)
36
(20)
145
(63)
250
(121)
6 in. 290
(143)
A19EBB-1C Warm Air Open high
SPST
100 to 350
(38 to 177)
9
(5)
36
(20)
240
(116)
350
(177)
6 in. 375
(191)
A19EBC-1C Counter-Flow
Warm Air Furnace
Single-Pole,
Double-Throw
(SPDT)
100 to 350
(38 to 177)
9
(5)
36
(20)
240
(116)
350
(177)
6 in. 375
(191)
A19EDB-1C
1
1. A19EDB-1 not for use as a limit control.
Warm Air
With Lock Out
Open high
SPST
100 to 350
(38 to 177)
Manual Reset 240
(116)
350
(177)
6 in. 375
(191)
Replacement Parts
Product Code Number Description
CVR28A-618R Visible scale cover
Electrical Ratings
Motor Ratings VAC 120 208 240 277
A19EBA, A19EBB
AC Full Load A 16.0 9.2 8.0
AC Locked Rotor A 96.0 55.2 48.0
AC Non-Inductive A 22.0 22.0 22.0 22.0
Pilot Duty 125 VA, 24 to 600 VAC
A19EBC
AC Full Load A 16.0 9.2 8.0
AC Locked Rotor A 96.0 55.2 48.0
AC Non-Inductive A 16.0 16.0 16.0 16.0
Pilot Duty 125 VA, 24 to 600 VAC
A19EDB
AC Full Load A 16.0 9.2 8.0
AC Locked Rotor A 96.0 55.2 48.0
AC Non-Inductive A 22.0 22.0 22.0 16.0
Pilot Duty 125 VA, 24 to 600 VAC
A19EBA, A19EBB, A19EBC
A19EDB Cutout Controls
(A19EDB not for use as cutout control)
Single-Stage Electromechanical Temperature Controls
Code No. LIT-1927075