Brochure

Table Of Contents
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc. www.johnsoncontrols.com
R-20
A19 Series Remote Bulb Control (Continued)
Single-Stage Electromechanical Temperature Controls
Accessories
A packing nut is available for closed tank application.
Specify the code number FTG13A-600R.
Bulb wells (WEL14A Series) are available for liquid immersion applications.
See the selection chart or the Bulb Wells Catalog Page (LIT-1922135).
Replacement Parts
Product Code Number Description
CVR28A-617R Concealed adjustment cover
CVR28A-618R Visible scale cover
KNB20A-602R Replacement Knob Kit
Technical Specifications
Electrical Ratings
Motor Ratings VAC 120 208 240
Wide Range – Adjustable Differential
AC Full Load A 16.0 9.2 8.0
AC Locked Rotor A 96.0 55.2 48.0
Non-Inductive A
1
1. SPST and N.O. contact of SPDT control;
SPDT N.C. contact- 16 amperes 120 to 277 VAC
22 A, 120 to 277 VAC
Pilot Duty 125 VA, 24 to 600 VAC
Fixed Differential and Close Differential
AC Full Load A 6.0 3.4 3.0
AC Locked Rotor A 36.0 20.4 18.0
Non-Inductive A 10 A, 24 to 277 VAC
Pilot Duty 125 VA, 24 to 277 VAC
Case Compensated – Fixed Differential A19AAC-4
AC Full Load A 16.0 9.2 8.0
AC Locked Rotor A 96.0 55.2 48.0
Non-Inductive A
1
22 A, 120 to 277 VAC
Pilot Duty 125 VA, 24 to 600 VAC
A19AAD-12
AC Full Load A 6.0 3.4 3.0
AC Locked Rotor A 36.0 20.4 18.0
Non-Inductive A 10 A, 24 to 277 VAC
Pilot Duty 125 VA, 24 to 277 VAC
Manual Reset
AC Full Load A 16.0 9.2 8.0
AC Locked Rotor A 96.0 55.2 48.0
Non-Inductive A 16.0 9.2 8.0
Pilot Duty 125 VA, 24 to 600 VAC