A19 Series Remote Bulb Control
Description
The A19 Series Controls are single-stage
temperature controls that incorporate
environmentally friendly liquid-filled sensing
elements.
Refer to the A19 Series Hot Water Heating
Controls Well Immersion Product Bulletin
(LIT-125025) for important product application
information.
A19 Series
Action on Increase
of Temperature
Y
B
R
Features
wide temperature ranges available
constant differential throughout the entire
range
compact enclosure
fixed or adjustable differential available
variety of sensing element styles
unaffected by cross-ambient conditions
Selection Charts
A19 Series Remote Bulb Control
1
1. Specify the control model code number, packing nut code number (if required), and bulb well code number (if required).
Product Code
Number
Switch
Action
Range
°F (°C)
Differential
F° (C°)
Bulb and
Capillary
Bulb Well No.
(Order
Separately)
Range
Adjuster
Max. Bulb
Temp. °F (°C)
Adjustable Differential (Wide Range)
A19ABA-40C
2
2. Replaces White-Rodgers® 1609-101
Single-Pole,
Single-Throw
(SPST)
Open low
-30 to 100 (-34 to 38) 3 to 12 (1.7 to 6.7) 3/8 in. x 4 in., 6 ft. capillary WEL14A-602R Screwdriver Slot 140 (60)
A19ABC-4C SPDT 50 to 130 (10 to 55) 3-1/2 to 14 (1.9 to 8) 3/8 in. x 5 in., 8 ft. capillary WEL14A-603R Knob 170 (77)
A19ABC-24C
3
3. Replaces White-Rodgers 1609-12, -13; Ranco® 010-1408, -1409, - 1410, -1490, 060-110; Honeywell® L6018C-1006, L6021A-1005, T675A-1011, -1508, -1516,
-1821, T4301A-1008, T6031A-1011, T6031A-1029
SPDT -30 to 100 (-34 to 38) 3 to 12 (1.7 to 6.7) 3/8 in. x 4 in., 8 ft. capillary WEL14A-602R Convertible 140 (60)
A19ABC-36C SPDT -30 to 100 (-34 to 38) 3 to 12 (1.7 to 6.7) 3/8 in. x 4 in., 20 ft. capillary WEL14A-602R Convertible 140 (60)
A19ABC-37C SPDT -30 to 100 (-34 to 38) 3 to 12 (1.7 to 6.7) 3/8 in. x 4 in., 10 ft. capillary WEL14A-602R Screwdriver slot 140 (60)
A19ABC-74C SPDT -30 to 100 (-34 to 38) 3 to 12 (1.7 to 6.7) 3/8 in. x 4 in., 6 ft. capillary WEL14A-602R Screwdriver slot 140 (60)
Fixed Differential
A19AAF-12C SPDT 25 to 225 (-4 to 107) 3-1/2 (1.9) 3/8 in. x 3 in., 10 ft. capillary WEL14A-602R Screwdriver slot 275 (135)
Fixed Differential (Case Compensated)
A19AAC-4C SPDT 0 to 80 (-18 to 27) 5 (2.8) 3/8 in. x 4 in., 6 ft. capillary WEL14A-602R Screwdriver slot 140 (60)
A19AAD-12C SPST
Open low
-30 to 50 (-34 to 10) 2-1/2 (1.4) 3/8 in. x 4 in., 7 ft. capillary WEL14A-602R Screwdriver slot 140 (60)
Fixed Differential (Close)
A19AAD-5C
4
4. Case-Compensated
SPST
Open low
30 to 50 (-1 to 10)
(Bulk Milk Cooler)
2-1/2 (1.4) 3/8 in. x 2-5/8 in.,
6 ft. capillary
WEL16A-601R Screwdriver slot 190 (88)
A19AAF-20C SPDT -30 to 100 (-34 to 38) 2-1/2 (1.4) 3/8 in. x 4 in., 6 ft. capillary WEL14A-602R Screwdriver slot 140 (60)
A19AAF-21C SPDT 40 to 90 (4 to 32) 1-1/2 (0.8) 3/8 in. x 5-3/4 in., 6 ft. capillary WEL14A-603R Screwdriver slot 140 (60)
Manual Reset
A19ACA-14C SPST
Open low
-30 to 100
(-34 to 38)
Manual reset 3/8 in. x 4 in.
6 ft capillary
WEL14A-602R Screwdriver slot 140 (60)
A19ACA-15C SPST
Open low
-30 to 100
(-34 to 38)
Manual reset 3/8 in. x 4 in.
10 ft capillary
WEL14A-602R Screwdriver slot 140 (60)
A19ADB-1C SPST
Open high
100 to 240
(38 to 116)
Manual reset 3/8 in. x 3-1/2 in.
6 ft capillary
WEL14A-602R Knob 290 (143)
A19ADB-38C SPST
Open high
100 to 240
(38 to 116)
Manual reset 3/8 in. x 4 in.
6 ft capillary
WEL14A-602R Screwdriver slot 290 (143)
A19ABC-24 Remote Bulb Control
Single-Stage Electromechanical Temperature Controls
Code No. LIT-1927010
Applications
The A19 is suitable for temperature
control in HVAC/R applications.