Brochure

Table Of Contents
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc. www.johnsoncontrols.com
R-207
System 450™ Reset Control Modules with Real-Time Clock
and Relay Output (Continued)
System 450 Control Series
Selection Chart
Refer to the System 450 Compatible Sensors, Transducers, and Accessories Catalog Page (LIT-1900662) for temperature sensors and humidity
sensors compatible with the System 450 Reset Control Modules. Reset Control Modules control temperature and humidity, but not pressure.
Technical Specifications
Reset System 450 Modules and Accessories Ordering Information
Product Code
Number
Product Description
C450RBN-3C Reset Control Module with LCD, Four-Button Touchpad UI, and SPDT relay output; provides one SPDT output relay. One A99BC-25C
temperature sensor with 0.25 m (9-1/4 in.) silicon leads and one A99BC-300C temperature sensor with 3 m (9 ft 10 in.) silicon leads are
included in the box with the Reset Control Module.
C450RCN-3C Reset Control Module with LCD, Four-Button Touchpad UI, and SPDT relay output; provides two SPDT output relays. One A99BC-25C
temperature sensor with 0.25 m (9-1/4 in.) silicon leads and one A99BC-300C temperature sensor with 3 m (9 ft 10 in.) silicon leads are
included in the box with the Reset Control Module.
BKT287-1R DIN Rail; 0.30 m (12 in.) long
BKT287-2R DIN Rail; 1 m (39-1/3 in.) long
BKT287-3R DIN Rail; 0.61 m (24 in.) long
BKT287-4R DIN Rail; 0.36 m (14 in.) long
PLT344-1R DIN Rail End Clamps (Two clamps)
WHA-C450-100C System 450 module connection extension cable, 100 cm (3.3 ft) long
C450RBN-3C and C450RCN-3C Reset Control Modules with Real-Time Clock and Relay Output
Product C450RBN-3C and C450RCN-3C: System 450 Reset Control Module models are sensing controls and operating
controls with LCD, four-button touchpad, and SPDT relay output
C450RBN-3C: Control Module with one SPDT output relay
C450RCN-3C: Control Module with two SPDT output relays
Power Consumption C450RBN-3C: 0.9 VA maximum
C450RCN-3C: 1.3 VA maximum
Supply Power Internal Supply Power: C450YNN-1C Power Supply Module
External Supply Power: 24 VAC (20 to 30 VAC) Safety Extra-Low Voltage (SELV) (Europe), Class 2 (North
America), 50/60 Hz, 10 VA minimum
Note: A System 450 control module or module assembly can use an internal or an external supply power source, but
must not be connected to both simultaneously.
Ambient Operating Conditions Temperature: -40 to 66C (-40 to 150F)
Humidity: Up to 95% RH noncondensing; maximum dew point 29C (85F)
Ambient Shipping and Storage Conditions Temperature: -40 to 80C (-40 to 176F)
Humidity: Up to 95% RH noncondensing; maximum dew point 29C (85F)
Input Signal 0 to 5 VDC for humidity sensors
1,035 ohms at 25C (77F) for A99 PTC temperature sensors
Output Relay Contacts General: 1/2 HP at 120/240 VAC, SPDT
Specific: AC Motor Ratings 120 VAC 208/240 VAC
AC Full-load Amperes: 9.8 A 4.9 A
AC Locked-Rotor Amperes: 58.8 A 29.4 A
_____________________________________
10 Amperes AC Non-inductive at 24/240 VAC
Pilot Duty: 125 VA at 24/240 VAC
Clock Accuracy ±4 minutes per year
Clock Backup Power 12 hours (capacitor reserve)
Setback Events One occupied and one unoccupied event per day; 7 day schedule
Analog Input Accuracy Resolution: 14 bits
Control Construction Independently mounted control, surface mounted with Lexan® 950 enclosure suitable for DIN rail mounting or direct
mounting to a hard, even surface.
Dimensions (H x W x D) 127 x 61 x 61 mm (5 x 2-3/8 x 2-3/8 in.)
Weight C450RBN-3C: 209 g (0.46 lb)
C450RCN-3C: 222 g (0.49 lb)
Compliance North America: cULus Listed; UL 60730, File E27734;
FCC Compliant to CFR47, Part 15, Subpart B, Class B;
Industry Canada (IC) Compliant to Canadian ICES-003, Class B limits
Europe: CE Mark – Johnson Controls, Inc. declares that this product is in compliance with the essential
requirements and other relevant provisions of the EMC Directive and the Low Voltage Directive.
Australia: Mark: C-Tick Compliant (N1813)