Brochure

Table Of Contents
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc. www.johnsoncontrols.com
R-201
System 450™ Series Modular Controls (Continued)
System 450 Control Series
C450RBN-3C and C450RCN-3C Reset Control Modules with Real-Time Clock and Relay Output (Part 2 of 2)
Input Signal 0 to 5 VDC for humidity sensors
1,035 ohms at 25C (77F) for A99 PTC temperature sensors
Output Relay Contacts General: 1/2 HP at 120/240 VAC, SPDT
Specific: AC Motor Ratings 120 VAC 208/240 VAC
AC Full-load Amperes: 9.8 A 4.9 A
AC Locked-Rotor Amperes: 58.8 A 29.4 A
_____________________________________
10 Amperes AC Non-inductive at 24/240 VAC
Pilot Duty: 125 VA at 24/240 VAC
Clock Accuracy ±4 minutes per year
Clock Backup Power 12 hours (capacitor reserve)
Setback Events One occupied and one unoccupied event per day; 7 day schedule
Analog Input Accuracy Resolution: 14 bits
Control Construction Independently mounted control, surface mounted with Lexan® 950 enclosure suitable for DIN rail mounting or direct
mounting to a hard, even surface.
Dimensions (H x W x D) 127 x 61 x 61 mm (5 x 2-3/8 x 2-3/8 in.)
Weight C450RBN-3C: 209 g (0.46 lb)
C450RCN-3C: 222 g (0.49 lb)
Compliance North America: cULus Listed; UL 60730, File E27734;
FCC Compliant to CFR47, Part 15, Subpart B, Class B;
Industry Canada (IC) Compliant to Canadian ICES-003, Class B limits
Europe: CE Mark – Johnson Controls, Inc. declares that this product is in compliance with the essential requirements
and other relevant provisions of the EMC Directive and the Low Voltage Directive.
Australia: Mark: C-Tick Compliant (N1813)
C450SPN-1C and C450SQN-1C Expansion Modules with Analog Output
Product C450SPN-1C: System 450 Expansion Module with one Analog output
C450SQN-1C: System 450 Expansion Module with two Analog outputs
Power Consumption C450SPN-1C: 1.1 VA max using 0 to 10 V out; 1.3 VA maximum using 4 to 20 mA out
C450SQN-1C: 1.8 VA max using 0 to 10 V out; 2.2 VA maximum using 4 to 20 mA out
Supply Power Internal Supply Power: C450YNN-1C Power Supply Module
External Supply Power: 24 VAC (20 to 30 VAC) Safety Extra-Low Voltage (SELV) (Europe), Class 2 (North America),
50/60 Hz, 10 VA minimum
Note: A System 450 control module or module assembly can use an internal or an external supply power source, but
must not be connected to both simultaneously.
Ambient Operating Conditions Temperature: -40 to 66C (-40 to 150F) when using 0 to 10 VDC outputs;
-40 to 40C (-40 to 104F) when using 4 to 20 mA outputs
Humidity: Up to 95% RH noncondensing; maximum dew point 29C (85F)
Ambient Shipping and Storage
Conditions
Temperature: -40 to 80C (-40 to 176F)
Humidity: Up to 95% RH noncondensing; maximum dew point 29C (85F)
Analog Output Voltage Mode (0 to 10 VDC):
10 VDC maximum output voltage
10 mA maximum output current
Requires an external load of 1,000 ohms or more
The AO operates in Voltage Mode when connected to devices with impedance greater than 1,000 ohms. Devices that
drop below 1,000 ohms may not operate as intended with Voltage Mode applications.
Current Mode (4 to 20 mA):
Requires an external load between 0 to 300 ohms
The AO operates in Current Mode when connected to devices with impedances less than 300 ohms. Devices that
exceed 300 ohms may not operate as intended with Current Mode applications.
Control Construction Independently mounted control, surface mounted with Lexan® 950 enclosure suitable for DIN rail mounting or direct
mounting to a hard, even surface.
Dimensions (H x W x D) 127 x 61 x 61 mm (5 x 2-3/8 x 2-3/8 in.)
Weight C450SPN-1C: 150 g (0.33 lb)
C450SQN-1C: 150 g (0.33 lb)
Compliance North America: cULus Listed; UL 60730, File E27734, Vol. 1; FCC Compliant to CFR47, Part 15, Subpart B, Class B
Industry Canada (IC) Compliant to Canadian ICES-003, Class B limits
Europe: CE Mark - Johnson Controls, Inc., declares that this product is in compliance with the essential requirements
and other relevant provisions of the Low Voltage Directive and the EMC Directive.
Australia: Mark: C-Tick Compliant (N1813)