Brochure

Table Of Contents
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc. www.johnsoncontrols.com
R-200
System 450™ Series Modular Controls (Continued)
System 450 Control Series
C450CPW-100C Control Module with Hybrid Analog Output (Part 2 of 2)
Compliance North America: cULus Listed; UL 60730, File E27734;
FCC Compliant to CFR47, Part 15, Subpart B, Class B
Industry Canada (IC) Compliant to Canadian ICES-003, Class B limits
Europe: CE Mark – Johnson Controls, Inc. declares that this product is in compliance with the essential requirements
and other relevant provisions of the EMC Directive and the Low Voltage Directive.
Australia: Mark: C-Tick Compliant (N1813)
C450CBN-3C and C450CCN-3C Control Modules with Relay Output
Product C450CBN-3C and C450CCN-3C: System 450 Control Module models are sensing controls and operating controls with
LCD, four-button touchpad, and SPDT relay output
C450CBN-3C: Control Module with one SPDT output relay
C450CCN-3C: Control Module with two SPDT output relays
Power Consumption C450CBN-3C: 0.9 VA maximum
C450CCN-3C: 1.3 VA maximum
Supply Power Internal Supply Power: C450YNN-1C Power Supply Module
External Supply Power: 24 VAC (20 to 30 VAC) Safety Extra-Low Voltage (SELV) (Europe), Class 2 (North America),
50/60 Hz, 10 VA minimum
Note: A System 450 control module or module assembly can use an internal or an external supply power source, but
must not be connected to both simultaneously.
Ambient Operating Conditions Temperature: -40 to 66C (-40 to 150F)
Humidity: Up to 95% RH noncondensing; maximum dew point 29C (85F)
Ambient Shipping and Storage
Conditions
Temperature: -40 to 80C (-40 to 176F)
Humidity: Up to 95% RH noncondensing; maximum dew point 29C (85F)
Input Signal 0 to 5 VDC for humidity sensors and static pressure transducers
0.5 to 4.5 VDC for ratiometric pressure transducers
1,035 ohms at 25C (77F) for A99 PTC temperature sensors
1,000 ohms at 21.1C (70F) for TE-6xxx Nickel temperature sensors
Output Relay Contacts General: 1/2 HP at 120/240 VAC, SPDT
Specific: AC Motor Ratings 120 VAC 208/240 VAC
AC Full-load Amperes: 9.8 A 4.9 A
Locked-Rotor Amperes: 58.8 A 29.4 A
_____________________________________
10 Amperes AC Non-inductive at 24/240 VAC
Pilot Duty: 125 VA at 24/240 VAC
Analog Input Accuracy Resolution: 14 bits
Control Construction Independently mounted control, surface mounted with Lexan® 950 enclosure suitable for DIN rail mounting or direct
mounting to a hard, even surface.
Dimensions (H x W x D) 127 x 61 x 61 mm (5 x 2-3/8 x 2-3/8 in.)
Weight C450CBN-3C: 209 g (0.46 lb)
C450CCN-3C: 222 g (0.49 lb)
Compliance North America: cULus Listed; UL 60730, File E27734;
FCC Compliant to CFR47, Part 15, Subpart B, Class B;
Industry Canada (IC) Compliant to Canadian ICES-003, Class B limits
Europe: CE Mark – Johnson Controls, Inc. declares that this product is in compliance with the essential requirements
and other relevant provisions of the EMC Directive and the Low Voltage Directive.
Australia: Mark: C-Tick Compliant (N1813)
C450RBN-3C and C450RCN-3C Reset Control Modules with Real-Time Clock and Relay Output (Part 1 of 2)
Product C450RBN-3C and C450RCN-3C: System 450 Reset Control Module models are sensing controls and operating
controls with LCD, four-button touchpad, and SPDT relay output
C450RBN-3C: Control Module with one SPDT output relay
C450RCN-3C: Control Module with two SPDT output relays
Power Consumption C450RBN-3C: 0.9 VA maximum
C450RCN-3C: 1.3 VA maximum
Supply Power Internal Supply Power: C450YNN-1C Power Supply Module
External Supply Power: 24 VAC (20 to 30 VAC) Safety Extra-Low Voltage (SELV) (Europe), Class 2 (North America),
50/60 Hz, 10 VA minimum
Note: A System 450 control module or module assembly can use an internal or an external supply power source, but
must not be connected to both simultaneously.
Ambient Operating Conditions Temperature: -40 to 66C (-40 to 150F)
Humidity: Up to 95% RH noncondensing; maximum dew point 29C (85F)
Ambient Shipping and Storage
Conditions
Temperature: -40 to 80C (-40 to 176F)
Humidity: Up to 95% RH noncondensing; maximum dew point 29C (85F)