System 450 Compatible P499 Series Transducers with 1/4 in. SAE 45 Flare Internal Thread with Depressor (Style 47) Ordering
Information
1
Product Code
Number
Product Description
P499RCP-401C -1 to 8 bar; order WHA-PKD3 type wire harness separately
P499RCP-402C -1 to 15 bar; order WH A-PKD3 type wire harness separately
P499RCP-404C 0 to 30 bar; order WHA-PKD3 type wire harness separately
P499RCP-405C 0 to 50 bar; order WHA-PKD3 type wire harness separately
P499RCPS100C -10 to 100 psis (sealed for wet and freeze/thaw applications); order WHA-PKD3 type wire harness separately
P499RCPS100K -10 to 100 psis (sealed for wet and freeze/thaw applications); WHA-PKD3-200C wire harness included
P499RCPS102C 0 to 200 psis (sealed for wet and freeze/thaw applications); order WHA-PKD3 type wire harness separately
P499RCPS102K 0 to 200 psis (sealed for wet and freeze/thaw applications); WHA-PKD3-200C wire harness included
P499RCP-101C 0 to 100 psi; order WHA-PKD3 type wire harness separately
P499RCP-101K 0 to 100 psi; WHA-PKD3-200C wire harness included
P499RCP-105C 0 to 500 psi; order WHA-PKD3 type wire harness separately
P499RCP-105K 0 to 500 psi; WHA-PKD3-200C wire harness included
P499RCP-107C 0 to 750 psi; order WHA-PKD3 type wire harness separately
P499RCP-107K 0 to 750 psi; WHA-PKD3-200C wire harness included
1. The P499 sensors must be powered with the +5 VDC and C terminals and the output is 0.5 to 4.5 VDC. Refer to the P499 Series Electronic Pressure
Transducers Product/Technical Bulletin (LIT-12011190) on the Johnson Controls Product Literature website for more information.
System 450 Compatible P499 Series Transducers with 1/8 in. 27 NPT External Thread (Style 49) Ordering Information
1
Product Code
Number
Product Description
P499RAPS100C -10 to 100 psis (sealed for wet and freeze/thaw applications); order WHA-PKD3 type wire harness separately
P499RAPS100K -10 to 100 psis (sealed for wet and freeze/thaw applications); WHA-PKD3-200C wire harness included
P499RAPS102C 0 to 200 psis (sealed for wet and freeze/thaw applications); order WHA-PKD3 type wire harness separately
P499RAPS102K 0 to 200 psis (sealed for wet and freeze/thaw applications); WHA-PKD3-200C wire harness included
P499RAP-101C 0 to 100 psi; order WHA-PKD3 type wire harness separately
P499RAP-101K 0 to 100 psi; WHA-PKD3-200C wire harness included
P499RAP-102C 0 to 200 psi; order WHA-PKD3 type wire harness separately
P499RAP-105C 0 to 500 psi; order WHA-PKD3 type wire harness separately
P499RAP-105K 0 to 500 psi; WHA-PKD3-200C wire harness included
P499RAP-107C 0 to 750 psi; order WHA-PKD3 type wire harness separately
P499RAP-107K 0 to 750 psi; WHA-PKD3-200C wire harness included
1. The P499 sensors must be powered with the +5 VDC and C terminals and the output is 0.5 to 4.5 VDC. Refer to the P499 Series Electronic Pressure
Transducers Product/Technical Bulletin (LIT-12011190) on the Johnson Controls Product Literature website for more information.
WHA-PKD3 Wire Harnesses Ordering Information
1
Product Code
Number
Product Description
WHA-PKD3-200C Plug and Three-Wire Harness for P499 Electronic Pressure Transducers: 2.0 m (6-1/2 ft) cable
WHA-PKD3-400C Plug and Three-Wire Harness for P499 Electronic Pressure Transducers: 4.0 m (13 ft) cable
WHA-PKD3-600C Plug and Three-Wire Harness for P499 Electronic Pressure Transducers: 6.0 m (19-5/8 ft) cable
1. Refer to the P499 Series Electronic Pressure Transducers Product/Technical Bulletin (LIT-12011190) on the Johnson Controls Product Literature website for
more information.
C450CPN-3C and C450CQN-3C Control Modules with Analog Output (Part 1 of 2)
Product C450CPN-3C and C450CQN-3C: System 450 Control Module models are sensing controls and operating controls with
LCD, four-button touchpad, and SPDT analog output
C450CPN-3C: Control Module with one analog output
C450CQN-3C: Control Module with two analog outputs
Power Consumption C450CPN-3C: 1.3 VA maximum using 0 to 10 V out; 1.5 VA maximum using 4 to 20 mA out
C450CQN-3C: 2.0 VA maximum using 0 to 10 V out; 2.4 VA maximum using 4 to 20 mA out
Supply Power Internal Supply Power: C450YNN-1C Power Supply Module
External Supply Power: 24 VAC (20 to 30 VAC) Safety Extra-Low Voltage (SELV) (Europe), Class 2 (North America),
50/60 Hz, 10 VA minimum
Note: A System 450 control module or module assembly can use an internal or an external supply power source, but
must not be connected to both simultaneously.