Brochure

Table Of Contents
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc. www.johnsoncontrols.com
R-191
Y63, Y64, Y65, Y66, and Y69 Series Transformers (Continued)
Relays and Transformers
Technical Specifications
75 VA Capacity Transformers with Circuit Breakers
Y66T12-0 120/208/240 24 Common External Fitting
8 in. primary leads
Common External Fitting
8 in. secondary leads
Foot cURus Class 2
Y66T13-0 120/208/240 24 External Fitting
8 in. primary leads
External Fitting
30 in. secondary leads
Foot cULus Class 2
Y66F12-0 277/480 24 Common External Fitting
8 in. primary leads
Common External Fitting
8 in. secondary leads
Foot cURus Class 2
Y66F13-0 277/480 24 External Fitting
8 in. primary leads
External Fitting
30 in. secondary leads
Foot cULus Class 2
92 VA Capacity Transformers with Circuit Breakers
Y64T15-0 120/208/240 24 External Fitting
8 in. primary leads
Internal Fitting
30 in. secondary leads
Foot cULus Class 2
Y64T21-0 120/208/240 24 End bell holes
8 in. primary leads
Three screw terminals
(one is blind)
Plate cULus Class 2
Y64T22-0 120/208/240 24 End bell Hole
8 in. primary leads
End bell Hole
8 in. secondary leads
Plate cURus Class 2
300 VA Capacity Transformers with Circuit Breakers
Y69T15-0 120/208/240 24 External Fitting
8 in. primary leads
Internal Fitting
30 in. secondary leads
Foot cULus
Power Transformer
1. 4 in. x 4 in. plate and nut packed with transformer.
Series Y63, Y64, Y65, Y66, Y69 Transformers
Input Power Requirements 24 to 480 VAC at 60 Hz
Full Load Secondary Voltage 23.5 VAC (Nominal)
Open Circuit Secondary Voltage (No Load) 27.0 VAC (Nominal)
Full Load Secondary VA Rating Series
Y63
Y64
Y65
Y66
Y69
Volt-Amperes
50 VA
92 VA
40 VA
75 VA
300 VA
Finish End bells, frame, feet, and mounting plates are corrosion resistant
Ambient Operating Temperature -40 to 104°F (-40 to 40°C)
Ambient Storage Temperature -40 to 140°F (-40 to 60°C)
Shipping Weight Y63
Y64
Y65
Y66
Y69
3.0 lb/1.4 kg
4.0 lb/1.8 kg
2.0 lb/0.9 kg
3.0 lb/1.4 kg
11.0 lb/5.0 kg
Agency Compliance UL Listed Y63, Y64, Y65, Y66; File E95575, CCN’s XOKV (US) and XOKV7 (Canada)
UL Recognized Y63, Y64, Y65, Y66; File E95575, CCN’s XOKV2 (US) and XOKV8 (Canada)
UL Listed Y69; File E95138, CCN’s XPTQ (US) and XPTQ7 (Canada)
All transformers are Class 2 except the Y69 (300 VA), which is listed as a power transformer.
Y63, Y64, Y65, Y66, and Y69 Series Transformers (Part 2 of 2)
Product Code
Number
Primary
Voltage
VAC
Secondary
Voltage
VAC
Primary
Connection
Secondary
Connection
Mounting Agency
Requirement