The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc. www.johnsoncontrols.com
R-165
V146 Series Two-Way Pressure-Actuated Water-Regulating Valves
(Continued)
Valves and Valve Accessories
Repair Information
If the V146 Series Two-Way Pressure-Actuated Water-Regulating Valve fails to operate within its specifications, refer to the V146 Series
Two-Way Pressure-Actuated Water-Regulating Valves Product Bulletin (LIT-1201709) for a list of repair parts available.
Technical Specifications
Selection Chart
Product Code Number Nominal Valve Size Inlet and Outlet Ports Pressure Connection
Style
Shipping Weight, lb (kg)
V146EK-1C 3/4 in. Union (Sweat) 46 4.3 (2.0)
V146GK1-001C 3/4 in. Union (Sweat) 5 4.3 (2.0)
V146AL-1C 1 in. Union (Sweat) 46 9.3 (4.0)
V146GL1-001C 1 in. Union (Sweat) 5 9.3 (4.0)
V146 Series 2-Way Pressure-Actuated Water-Regulating Valves
Maximum Refrigerant Pressure V146EK: 370 psi (25.5 bar)
V146AL: 320 psi (22.1 bar)
Maximum Working Pressure V146GK1, V146GL1: 630 psi (43.4 bar)
Opening Point Adjustment Range V146EK, V146AL: 70 to 260 psi (4.8 to 17.9 bar)
V146GK1, V146GL1: 200 to 400 psi (13.8 to 27.6 bar)
Factory-Set Opening Point V146EK, V146AL: 165 psi (11.4 bar)
V146GK1, V146GL1: 275 psi (19.0 bar)
Media 350 psi (24.1 bar) maximum,
-4F to 170F (-20C to 77C) glycol/water or liquids with low freezing points that are compatible with valve materials
Pressure Connection Styles
Style 5
Style 46
1/4-in. SAE External Flare Connector
Copper Capillary with
1/4-in. SAE Internal Flare Connector
(Includes Valve Stem Depressor)