V47N Series Reverse Acting Valve
Description
The V47N Series are reverse-acting,
temperature-actuated, modulating valves that
regulate the flow of water or glycol to maintain
a desired temperature. Reverse-acting valves
open on a drop in temperature. They are
generally used in parallel with direct-acting
valves for hand pump applications or for
bypass operation.
Refer to the V47 Series Temperature
Actuated Modulating Water Valves Product
Bulletin (LIT-125690) for important product
application information.
Applications
bypass systems
water-cooled heat pumps in parallel with a
direct-acting valve
Selection Charts
V47N Series Reverse Acting Valve
Product Code
Number
1
1. Refer to sizing information in V47 Series Temperature Actuated Modulating Valve (LIT-1927330), then specify the code number from this chart.
Pipe Size & Connector Opening Point
Range
Factory-set
Opening Point
Bulb Size,
In.
Standard Bypass
Orifice
V47NB-1C 1/2 in. Screw 85 to 155°F 105°F 11/16 x 3-1/4
V47NC-1C 3/4 in. Screw
V47NR-1C 1-1/2 in. Flange 45 to 85°F 55°F 11/16 x 16-1/4
Repair Parts and Accessories
Parts For: Product Code Number
Seat Repair Kit Replacement Sensing
Element
Bulb Well Number
(Order Separately)
V47NB-1C STT15A-602R
WEL18A-602R (Brass)
V47NC-1C STT16A-601R
V47NR-1C STT17A-610R SET29A-605R
Code No. LIT-1900107