R-151
V46 Series Pressure Actuated Water Regulating Valve
Code No. LIT-1927350
Description
The V46 is a pressure actuated modulating valve that is suitable for
use either on closed or open systems. Direct acting valves open on
pressure increase. This type of valve is primarily used to regulate
the flow of water or glycol to a water cooled condenser on a
refrigeration system.
Refer to the V46 Pressure-Actuated Water-Regulating Valve
Product Bulletin (LIT-125687) for important product application
information.
Features
no close fitting or sliding parts in water passages
minimizes chatter or water hammer
free movement of all parts provides smooth pressure
modulation
refrigerant adjustment is not affected by water pressure
withstands high hydraulic shock without damage
range spring does not come in contact with cooling water
easy manual flushing, if required
3/8, 1/2, and 3/4 in. valves may be disassembled and
reassembled without detaching from the refrigeration system or
without pumping down
Applications
This valve is designed to modulate flow of water or glycol to a water
cooled condenser on a refrigeration system.
ice machines
computer room air conditioning units
ice cream machines
refrigeration cases
Selection Chart
Product Code
Number
1
Pipe
Size
(In.)
Inlet and
Outlet
Opening Point
Range – psig (kPa)
Pressure Element
Style
2
Seat Repair
Kit
Replacement
Power Elements
Commercial Type, Standard Flow - Non-Corrosive Refrigerant
V46AA-1C 3/8 NPT Threaded 70 to 260 (483 to 1,793) 30 in Capillary; 1/4 in. Flare Nut (Style 45) STT14A-600R SEP91A-600R and
SEC99AA-36C
3
V46AA-50C 1/4 in. External Flare Fitting (Style 5) SEP91A-600R
V46AB-1C 1/2 NPT 30 in Capillary; 1/4 in. Flare Nut (Style 45) STT15A-602R SEP91A-602R and
SEC99AA-36C
3
V46AB-25C 1/4 in. External Flare Fitting (Style 5) SEP91A-602R
V46AC-1C 3/4 NPT 30 in Capillary; 1/4 in. Flare Nut (Style 45) STT16A-601R SEP91A-601R and
SEC99AA-36C
3
V46AC-26C 1/4 in. External Flare Fitting (Style 5) SEP91A-601R
V46AD-1C 1 NPT 30 in Capillary; 1/4 in. Flare Nut (Style 45) STT17A-609R SEP91A-603R and
SEC99AA-36C
3
V46AD-13C 1/4 in. External Flare Fitting (Style 5) SEP91A-603R
V46AE-1C 1 1/4 NPT 30 in Capillary; 1/4 in. Flare Nut (Style 45) STT17A-610R SEP91A-603R and
SEC99AA-36C
3
V46AE-17C 1/4 in. External Flare Fitting (Style 5) SEP91A-603R
V46AJ-2C 1/2 Union 48 in Capillary; 1/4 in. Flare Nut (Style 46) STT15A-602R SEP77A-605R
V46EK-2C 3/4 STT16A-601R SEP127A-600R
V46AL-2C 1 STT17A-609R SEP107A-602R
V46AM-2C 1-1/4 STT17A-610R
V46AR-1C 1 1/2 Four Hole
ASME Flange
30 in Capillary; 1/4 in. Flare Nut (Style 45) SEP91A-603R and
SEC99AA-36C
3
V46AR-10C 1/4 in. External Flare
Fitting (Style 5)
(see Note below)
SEP91A-603R
V46AS-1C 2 70 to 170 (483 to 1,172) STT18A-600R SEP81A-602R
V46AS-2C 2 160 to 260 (1,103 to 1,793) SEP81A-601R
V46AT-1C 2-1/2 70 to 170 (483 to 1,172) STT18A-601R SEP81A-602R
V46AT-2C 2-1/2 160 to 260 (1,103 to 1,793) SEP81A-601R
V46AA-1 Water
Regulating Valve
V46AT-1 Water
Regulating Valve
Valves and Valve Accessories
Repair Information
If the V46 Series Pressure Actuated Water Regulating Valve fails to
operate within its specifications, replace the unit. For a replacement
valve, contact the nearest Johnson
Controls®