Brochure

Table Of Contents
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc. www.johnsoncontrols.com
R–129
F261 Series Fluid Flow Switches (Continued)
Liquid Level and Flow Controls
UL Conformity Declaration Information
Information Description
Purpose of Control F261 Fluid Flow Switch
Construction of Control Electronic independently mounted control
Number of Cycles 100,000 cycles
Method of Mounting Control Mounting to sensed media vessel/orientation
Type 1 or Type 2 Action Type 1.C (Microinterruption)
External Pollution Situation Pollution degree 4
Internal Pollution Situation Pollution degree 2
Rated Impulse Voltage 4,000 VAC
Ball Pressure Temperature Enclosure: 266°F (130°C)
Switch Component: 252°F (122°C)
Control Adjustment Instruction -
Field Wiring Rating Wire/Cord Temperature Ratings:
140°F (60°C) only permitted when ambient air and media are less than 113°F (45°C)
167°F (75°C) only permitted when ambient air and media are less than 140°F (60°C)
194°F (90°C) only permitted when ambient air is less than 140°F (60°C) and media is less than 167°F (75°C)
302°F (150°C) permitted when ambient air is less than 140°F (60°C) and media is less than 249°F (121°C)
Vessel Pressure F261 Fluid Flow Switch: 290 psi (20 Bar)
F261 Series Fluid Flow Switches
Switch Single-Pole, Double-Throw (SPDT)
Enclosure UL: Type 3R or Type 4
CE: IP43 (IP23 with drain hole plug removed) or IP67
Wiring Connections Three color-coded screw terminals and one ground terminal
Conduit Connection One 7/8 in. (22 mm) hole for 1/2 in. trade size (or PG16) conduit
Pipe Connector Standard: 1 in. 11-1/2 NPT Threads
Maximum Fluid Pressure 290 psi (20 bar)
Minimum Fluid Temperature
1
1. Ensure that the low liquid temperature combined with the low ambient temperature does not lead to the freezing the liquid inside the body (or bellows, where
appropriate). Please observe the liquid freezing point.
-20°F (-29°C)
Maximum Fluid Temperature
2
2. At higher ambient temperatures, the maximum allowed liquid temperature becomes lower. The temperature of the electrical switch inside should not exceed
158°F (70°C).
250°F (121°C)
Ambient Conditions -40 to 140°F (-40 to 60°C)
Compliance North America: cULus Listed; UL 60730, File E6688;
FCC Compliant to CFR47, Part 15, Subpart B, Class B
Industry Canada (IC) Compliant to Canadian ICES-003, Class B limits
Europe: CE Mark – Johnson Controls, Inc. declares that this product is in compliance with the essential requirements and
other relevant provisions of the EMC Directive and the Low Voltage Directive.
Australia/New Zealand Mark: RCM Compliant