Brochure

Table Of Contents
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc. www.johnsoncontrols.com
R-125
RLD-H10PRO Refrigerant Leak Detector
Code No. LIT-1900954
Description
The RLD-H10PRO is a professional-grade
leak detector for use by refrigeration and air
conditioning technicians. This detector
senses all CFC, HCFC, and HFC refrigerants
and blends, such as R12, R22, R134a,
R404a, R410a, R502, and R507 among
others. The RLD-H10PRO is self-powered
with a rechargeable battery and provides both
manual and automatic compensation for
background levels of refrigerant. A full line of
accessories and maintenance kits are also
available, including replacement sensors,
tuneup kits, probe extensions, battery
chargers, and leak vial bottles.
Refer to the RLD-H10PRO Refrigerant Leak
Detector Product Bulletin (LIT-12012073) for
important product application information.
Features
positive ion emission heated diode sensor
provides the most sensitivity available
today, while still detecting all halogenated
refrigerant gases
rechargeable battery with low and full
charge LEDs enhances portability—no
external power required
high quality air pump supplies constant
airflow to the sensor so it responds quickly
to leaks; also helps the sensor recover
quickly after exposure to a refrigerant so
the leak can be verified
switchable adjustment for manual or
automatic balance allows users to choose
their preferred method of compensation for
background refrigerant levels
visual and audible signal facilitates
sensing in noisy equipment rooms with
360° visibility and a piercing tone.
Frequency of noise and light indicates the
magnitude of the leak.
headset jack allows users to hear the leak
detector response in noisy environments
external calibration source and calibration
indicators indicate when the sensor is
working properly and serves as a
reference point to judge leak size
Selection Chart
Accessories
Product Code
Number
Description
RLD-H10PRO-1 Refrigerant leak detector and
charger
Product Code
Number
Description
RLD-H10-100 14 inch flexible probe extension
RLD-H10-101 120 VAC power supply adaptor
RLD-H10-102 Cigarette lighter adaptor
RLD-H10-103 Replacement battery charger
RLD-H10-105 Belt pack battery
RLD-H10-600R Tuneup kit: includes sensor,
100 filters, three airflow balls,
three rubber probe tips, and
leak vial
RLD-H10-601R Replacement sensor
RLD-H10-602R Maintenance kit: includes
100 filters, three airflow balls,
three rubber probe tips, and
leak vial
RLD-H10-603R Replacement leak vial
RLD-H10-604R Replacement for RLD-H10PRO
internal battery
RLD-H10-606R Clear plastic probe tip
RLD-H10-607R Probe replacement assembly
Technical Specifications
RLD-H10PRO Refrigerant Leak Detector
Power Requirements 12 VDC internal battery, or 100 to 240 VAC input/18 V output wall adaptor
(included) (RLD-H10-101).
Sensing Element Type Positive ion emission heated diode
Approximate
Sensitivity
1
1. Sensitivity for R12, R22, R134a, R410a, R404a, and R507 when unit is set to small leak setting, manual
mode.
Stationary 0.006 oz./yr
Moving (Per SAE
J2791)
0.1 oz./yr
Automatic Background
Adjustment
Mode selection for automatic or manual background zeroing
Manual background zeroing provides the best sensitivity.
Leak Alarm Audible alarm (through internal beeper or stereo headphone jack), visible red
LED
Response Time Approximately 1 second
Warmup Time Approximately 2 minutes
Probe Length Approximately 4-1/2 ft (1.4 m)
Ambient Operating
Conditions
32 to 104°F (0 to 40°C); 5-90% RH, noncondensing
Ambient Storage
Conditions
14 to 140°F (-10 to 60°C); 5-90% RH, noncondensing
Case Rugged high-density polyethylene
Dimensions (H x W x D) 5-2/5 x 10-1/2 x 8-3/10 in. (137 x 267 x 211 mm)
Compliance
Europe: CE Mark Johnson Controls, Inc. declares that this product is in
compliance with the essential requirements and other relevant provisions of the
EMC Directive 2004/108/EC.
Shipping Weight 5.1 lb (2.3 kg)
RLD-H10PRO Refrigerant Leak
Detector
Refrigerant Sensors/Monitors
Repair Information
If the RLD-H10PRO Refrigerant Leak Detector
fails to operate within its specifications,
contact
Johnson Controls® application engineering at