P100 Series Encapsulated Pressure Switches
Description
P100 Series switches are encapsulated,
nonadjustable, single-pole, single-throw
(SPST), direct-mount switches for use with
non-corrosive refrigerants. The switches are
available with automatic reset in both open
low and open high configurations and manual
reset with open high action.
Refer to the P100 Series Encapsulated
Pressure Controls Product Bulletin
(LIT-121485) for important product
application information.
Features
compact size and light weight allow for
direct mounting
trip-free manual reset (manual reset
models); contacts cannot be overridden by
continued depression of the reset button
use with all non-corrosive refrigerants
encapsulated switch, dust tight
1/4 in. Internal flare fitting with built-in
Schrader type depressor is standard
electrical connections are made to 48 in.
leads
Applications
low limit, high limit, and fan cycling control
in commercial refrigeration
ice machines
food service equipment
Repair Information
If the P100 Series Encapsulated Pressure
Switches fails to operate within its
specifications, replace the unit. For a
replacement switch, contact the nearest
Johnson
Controls®
representative.
P100 Series Encapsulated
Pressure Switch
Technical Specifications
Standard Duty Electrical Contact Ratings
Switch Action-Model
Numbers
SPST-P100AA, AC, AG, AJ, CA, CC, CG, CJ, DA, and
DC
SPST-P100AP, CP
Motor Ratings 120V 240V 120V 240V
AC Full Load Ampere 5.8 2.9 6.0 6.0
AC Locked Rotor
Ampere
34.8 15.0 36.0 36.0
Non-Inductive Ampere ----
Inductive Ampere ----
Pilot Duty 375 VA 375 VA
Heavy Duty Electrical Contact Ratings
Switch Action-Model
Numbers
SPST-P100AE and CE SPDT-P100EE
Motor Ratings 120V 240V 120V 240V
Contact Type N.O. N.C. N.O. N.C. N.O. N.C. N.O. N.C.
AC Full Load Ampere 13.0 13.0 10.0 10.0 5.8 13.0 2.9 10.0
AC Locked Rotor
Ampere
65.0 60.0 45.0 45.0 34.8 60.0 17.4 45.0
Non-Inductive Ampere 13.0 25.0 10.0 25.0 10.0 25.0 5.0 25.0
Inductive Ampere 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
Pilot Duty 278 VA 125 VA 278 VA 125 VA 278 VA 125 VA 278 VA 125 VA
Pressure Sensors and Accessories
Code No. LIT-1927275