Brochure

Table Of Contents
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc. www.johnsoncontrols.com
R-112
P545 Series Electronic Lube Oil Control (Continued)
Electronic Lube Oil and Differential Pressure Controls
Accessories
Technical Specifications
P400 Single-Point Differential Lube Oil Pressure Switch
Product Code
Number
1
1. Wiring harness included
Open Point
(Differential
Pressure)
Close Point
(Differential Above
Open Point)
Threads Wiring
Harness
P400AD-1C 7.0 ±1.0 psi less than or equal to 2.0 psi 3/4-16 UNF WHA-P400-100
P400AD-2C 12.75 ±0.75 psi less than or equal to 1.5 psi
P400BD-1C 10.0 ±1.5 psi less than or equal to 3.0 psi M20 x 1.5 WHA-P400-125
Wiring Harnesses and Other Accessories
Product Code Number Description
KITP545-82C
1
1. Contact Carlyle Compressor Co. at 1-800-462-2759 to order Sensor Block Gasket 06DA680063.
CST29A-600C Sensor Block;
P545NCB-82 Control;
P400AD-1C Switch;
WHA-P400-100C Wiring Harness
WHA-P400-100C 3-1/3 ft (1 m) length wiring harness
WHA-P400-125C 4 ft (1-1/4 m) length wiring harness
WHA-P400-250C 8 ft (2-1/2 m) length wiring harness
WHA-P400-430C 14 ft (4-1/3 m) length wiring harness
R310AD-1C Low-voltage Current Sensing Switch
271-51 Universal Mounting Bracket
P545NCB Electronic Lube Oil Control
Power Requirements 120 or 240 VAC, 50/60 Hz +10%, -15%; power consumption: 3 VA
Open Point (Differential Pressure) P545NCB-22/P400AD-2: 12.75 ± 0.75 psi (87.9 ± 5.17 kPa)
P545NCB-25/P400BD-1: 10 ± 1.5 psi (68.9 ± 10.3 kPa)
P545NCB-82 P400AD-1: 7 ± 1.0 psi (48.2 ± 6.9 kPa)
Lube Oil Time Delay (Factory Settings) P545NCB-22: 120 ± 15 seconds
P545NCB-25: 90 ± 12 seconds
P545NCB-82: 120 ± 15 seconds
Anti-Short Cycle Timer Four selectable positions: 0, 35, 65, and 100 seconds (nominal times)
Type of Refrigerant Non-corrosive refrigerants only
Electrical Connections Control: Screw type terminals on a barrier terminal strip
Sensor: Snap-connect at sensor end, three-pin plug at control end
Maximum Electrical Rating Isolated relay output to compressor contactor (M-1 and M-2)
Pilot duty 375 VA at 120 VAC, 750 VA at 240 VAC
Alarm Circuit (Relay) NOA contact: Pilot duty 125 VA at 120/240 VAC; 60 W tungsten at 120/240 VAC
NCA contact: Pilot duty 125 VA at 120 VAC, 250 VA at 240 VAC
Backplate Material
Case and Cover Material
0.062 in. (1 mm) cold rolled steel
High impact thermoplastic
Ambient Operating Conditions -40 to 131°F (-40 to 5°C)
Ambient Storage Conditions -40 to 185°F (-40 to 85°C)
Approximate Shipping Weight 1.80 lb (0.82 kg)
Agency Listings UL Listed, File SA516, CCN SDFY
UL Listed for Canada, File SA516, CCN SDFY7