Brochure

Table Of Contents
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc. www.johnsoncontrols.com
R-110
P12AA
Differential Pressure Control
P12 Series Differential Pressure Controls
Description
The P12 Series Differential Pressure Controls
are suitable for use with oil and/or
non-corrosive refrigerants. The switch is
actuated by a difference in pressure between
the two sensing elements. The control is
factory-set to open the switch (COM to 1) at a
differential pressure of 18 psi (124 kPa) and
close the switch (COM to 1) at a differential
pressure of 12 psi (83 kPa). The control is not
field-adjustable.
This control may be connected to a P28 Lube
Oil Control, with time delay, to give complete
monitoring of lubrication on two refrigeration
compressors driven by one motor.
Refer to the P12 Series Differential Pressure
Control Product Bulletin (LIT-997452) for
important product application information.
Repair Information
If the P12 Series Differential Pressure Control
fails to operate within its specifications, replace
the unit. For a replacement control, contact the
nearest Johnson
Controls®
representative.
Selection Chart
Product Code
Number
Differential Pressure Maximum
Overpressure, psi (kPa)
Enclosure Fitting
COM to 1 OPENS COM to 1 CLOSES
P12AA-3C 18 psi (124 kPa) 12 psi (83 kPa) 500 (3,447) NEMA1 Enclosure 1/4 in. external SAE flare fitting
Electromechanical Lube Oil and Differential Pressure Controls
Code No. LIT-1900115