The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc. www.johnsoncontrols.com
R-104
P470 Electronic Pressure Control with Display (Continued)
Single-Stage Electronic Pressure Controls
Technical Specifications
Output Relay Contacts Electrical Ratings
P470EB-1 P470 FB-1
120 VAC 208 VAC 240 VAC 24 VAC
Horsepower N.O. (N.C.) 1 (1/4) 1 (1/3) 1 (1/2) 100 VA,
30 VAC maximum,
Class 2
Full Load Ampere N.O. (N.C.) 16 (5.8) 9.2 (4.0) 8.0 (4.9)
Locked Rotor Ampere N.O. (N.C.) 96 (34.8) 55.2 (24) 498 (29.4)
Non-Inductive Ampere N.O. (N.C.) 15 (10) 10 (10) 10 (10)
Pilot Duty 125 VA (N.O.) at 24 to 240 VAC
125 VA (N.C.) at 120 to 240 VAC
50 VA (N.C.) at 24 VAC
P470 Electronic Pressure Control with Display
Operating Pressure Ranges 0 to 100 psi 0 to 500 psi 50 to 750 psi
Minimum Differential Pressure 5 psig 20 psig 20 psig
Displayed Resolution 1 psig 3 psig 5 psig
Control Accuracy +
1.5% of selected Operating Pressure Range plus transducer accuracy
Supply Voltage P470FB-1:24 VAC, 50/60 Hz, Class 2
P470EB-1:120 or 208/240 VAC, 50/60 Hz
Power Consumption 1.8 VA maximum
Transducer Type P499 Electronic Pressure Transducer
Ambient Temperature at Control Operating: -30 to 140°F (-34 to 60°C)
Shipping: -40 to 185°F (-40 to 85°C)
Ambient Humidity at Operating
Control
0 to 95% RH noncondensing;
Maximum dew point: 85°F (29°C)
Enclosure Case and cover: NEMA 1 High-impact thermoplastic
Agency Information UL: File SA516; CCN SDFY Canadian UL: File SA516; CCN SDFY7
FCC/DOC Part 15, Class A