P70, P72, and P170 Series Controls for Dual Pressure Applications
Description
The P70, P72, and P170 Controls for Dual
Pressure Applications are designed primarily
for use as combination high and low pressure
controls on commercial refrigeration and air
conditioning applications.
These controls are available in several
pressure ranges and are compatible with most
common refrigerants. Ammonia compatible
models are also available.
These controls respond directly to system
pressure changes on both high and low sides,
and can provide single-device control of the
compressor.
Controls are available in several different
electrical ratings and switch configurations,
including independent high and low pressure
switches (on P70S and P170S models). The
P72 models provide direct control of
208 to 240 volt, single-phase motors up to
three horsepower, and 208 to 220 volt,
three-phase motors up to five horsepower.
Refer to the P70, P72, and P170 Series
Controls for Dual Pressure Applications
Product Bulletin (LIT-125455) for important
product application information.
Features
all-steel case and cover built to provide
long lasting, rugged protection for internal
components
sight-set calibrated pressure adjustment
displays a visible pressure scale, fully
adjustable through the range without
removing the cover (on NEMA 1 enclosure
models)
MICRO-SET™ differential option allows for
precise control on low pressure
applications
independent high and low pressure
switches (P70S and P170S Models)
satisfies a variety of dual pressure
application wiring requirements with a
single versatile control
convertible high pressure reset–auto reset
or manual reset lockout (P70S and P170S
Models) reduces inventory—one control
can be adapted to several dual pressure
applications in the field
Applications
P70S and P170S models have
independently operated high and low
pressure single-pole, double-throw (SPDT)
switches that can be wired to satisfy a
variety of control requirements. These
adaptable controls also come with a high
pressure manual reset lockout mechanism
that may be converted to automatic reset.
P70L, M, N, and P170L, M, N models
have a single-pole, single-throw (SPST)
switch. Models are available with
automatic or manual reset lockout options.
Models with manual reset are available
with either high-side-only manual reset, or
low-side and high-side manual reset.
Ammonia-compatible models are also
available (P70L and P70M only).
P72 models have a double-pole,
single-throw (DPST) switch with
load-carrying contacts that can provide
direct control of 208 to 240 VAC,
single-phase motors up to 3 hp, and 208 to
220 VAC, three-phase motors up to 5 hp.
See the DPST Electrical Ratings (P72L, M,
and N Types) that follow.
Some models are available with Limited
Knob Adjustment, which restricts adjustment
of the pressure settings and deters
over-adjustment or tampering.
NEMA 1 enclosures are standard on most
models. NEMA 3R enclosures are also
available.
Repair Information
If the P70, P72, and P170 Series Controls for
Dual Pressure Applications fail to operate
within its specifications, replace the unit. For a
replacement control, contact the nearest
Johnson
Controls®
representative.
Selection Chart (Part 1 of 2)
Product Code
Number
Switch
Action
Low Pressure Side psi (kPa) High Pressure Side psi (kPa) Pressure
Connector
Limited Knob
Adjustment
Range Differential Range Differential (Non-Adjustable)
MICRO-SET Controls for Non-Corrosive Refrigerants
P70LB-6C
1
SPST 12 in.Hg
to 80
(-41 to 552)
Minimum 5 (34)
Maximum 35 (241)
100 to 500
(690 to 3,447)
Fixed approx. 65 (448) 36 in.
capillary with
1/4 in. flare
nut
Low cut-out
P70MA-1C
1
Lockout requires manual reset None
P70SA-1C
1
Two independent
SPDT
Fixed at 65 (448) or
Lockout requires manual reset
P170LB-6C
1
SPST Fixed approx. 65 (448) 1/4 in.
external flare
connector
Low cut-out
P170MA-18C
1
Lockout requires manual reset None
P170SA-1C
1
Two independent
SPDT
Fixed at 65 (448) or
Lockout requires manual reset
All Range Controls for Non-Corrosive Refrigerants
P70LB-1C
1
SPST 20 in.Hg
to 100
(-68 to 690)
Minimum 6 (41)
Maximum 50 (345)
100 to 500
(690 to 3,447)
Fixed Approx. 65 (448) 36 in.
capillary with
1/4 in. flare
nut
Low cut-out
P70MA-1C
1
Lockout Requires Manual Reset None
P70NA-1C Fixed (manual reset)
P72LA-1C
1
DPST Minimum 7 (48)
Maximum 50 (345)
Fixed approx. 65 (448)
P72LB-1C
1
Low cut-out
P72MA-1C
1
Lockout requires manual reset None
P72NA-1C
1
Fixed (manual reset)
P70MA-1 Dual Pressure Control