Install Instructions

Air DryersA-4400 Series Technical Bulletin 3
Introduction
The A-4400 Series Refrigerated Air Dryers are designed for continuous
operation to supply dry air to pneumatic control systems. All components
are selected and assembled to provide dependable service over a long
period of time with a minimum amount of maintenance.
Note: For units without a factory mounted Air Purification System
(consisting of a coalescing oil removal filter with integral
pressure drop indicator, packed column type activated carbon oil
vapor removal filter, service bypass valve, pressure reducing valve,
safety relief valve, and power on/fail lamp), a properly configured
system must include a coalescing oil removal filter as well as an
activated carbon oil vapor removal filter as outlined in Product
Data A-4000 and the Installation and Service Manual for
PureFlow Air Compressors (Publication No. 2629).
Table 1: Ordering Data
Code
Number
Flow Capacity at
Rated Condition*
scfm
(L/s)
Air
Purification
System
Shipping
Weight
lb**
A-4412-1
12
(5.7)
Yes
72
A-4412-2
12
(5.7)
No
67
A-4417-1
17
(8.0)
Yes
78
A-4417-2
17
(8.0)
No
73
A-4423-1
23
(10.9)
Yes
78
A-4423-2
23
(10.9)
No
72
Product
Overview