Operation Manual

T600MSx-3 Multi-Stage Thermostat Installation Instructions8
H lock Discontinues heating operation in
response to the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
Default: 120°F/49°C
Range: -15°F/-26°C to 120°F/49°C adjustable in 5F°/5C° increments
C lock Discontinues cooling operation in
response to the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
Default: -40°F/-40°C
Range: -40°F/-40°C to 95°F/35°C adjustable in 5F°/5C° increments
2/4event
4
Sets the number of events within a
24-hour period.
Default: 2.0
(2.0): Two events (one occupied and one unoccupied) within a
24-hour period
(4.0): Four events (two occupied and two unoccupied) within a
24-hour period
Aux cont Energizes peripheral devices
(lighting equipment, exhaust fans,
and economizers).
Default: n.o.
(n.c.): Contact open = Occupied; contact closed = Unoccupied
(n.o.): Contact closed = Occupied; contact open = Unoccupied
The contact toggles with the internal Occupied/Unoccupied
schedule (or the NSB contact on one of the digital inputs, if used).
Prog rec
4
Provides the desired occupied
temperature either at the start of the
occupied schedule or after the
occupied schedule begins.
Note: Progressive recovery is
disabled if either DI1 or DI2
is configured as remote
NSB.
Default: off
(on): Enabled (provides the desired occupied temperature at the
start of the occupied schedule)
(off): Disabled (provides the desired occupied temperature after the
occupied schedule begins)
1. Setting DI1 or DI2 to RemNSB disables schedules and stops the Schedule menu display. Any other setting enables
schedules and the Schedule menu. (T600MSP-3 only)
2. When adjusting the numeric value, press the UP or DOWN arrow key to change the value by single increments; press and
hold the UP or DOWN arrow key to change the numeric value in increments of ten.
3. When adjusting the temperature, press the UP or DOWN arrow key to change the value in 0.5F°/0.5C° increments; press
and hold the UP or DOWN arrow key to change the value in 5.0F°/5.0C° increments.
4. T600MSP-3 only
Table 2: Installer Configuration Menu (Part 4 of 4)
Parameter
Appearing
on Display
Description and Default Selection Options