Operation Manual

T600HCx-3 Single-Stage Thermostats Installation Instructions 3
To wire the thermostat:
1. Strip the ends of each wire a 1/4 in. (6 mm) and
connect them to the appropriate screw terminals as
indicated in Figure 5.
2. Carefully push any excess wire back into the wall.
Seal the hole in the wall with fireproof material to
prevent drafts from affecting the ambient
temperature readings.
3. Reinsert the screw terminal blocks onto the PCB.
4. Reattach the thermostat cover to the mounting
base (top side first).
5. Use a Phillips-head screwdriver to reinstall the
security screw on the bottom of the thermostat
cover.
Figure 5: Terminal Blocks
4 pole left top connector
2 pole right top connector
Y1 G RC
C
RH W1
D1 D2 RS
Scom
6 pole bottom connector
OS
MS
AUX
2
34
56
7
10 11 12 14
15
1613
F
I
G
:
T
6
0
0
H
C
x
_
t
r
m
b
l
k
Figure 6: Wiring the T600HCx-3 Thermostats
Cool 1
Fan
24 VAC
Thermostat Power
Heat 1
Y1
GRCC
RH W1
AUX
D1
D2
Scom
RS
Aux
If using the same power source
for the thermostat and heating
loads, install a jumper
across RC and RH.
Remote
Room
Sensor
Remote
Outdoor
Sensor
OS
F
I
G
:
T
6
0
0
H
C
P
_
w
i
r
Isolated Contact
- Lighting
- On/Off Actuation
- Exhaust Fan
Table 1: Terminal Identification (See Figure 5.)
Number Label Function
2Y1Energizes on a call for cooling.
3GEnergizes fan in accordance with
selected fan mode.
4RC24 VAC from equipment transformer
5C24 VAC (Common) from equipment
transformer
6RH24 VAC for heating stage
7W1Energizes on a call for heating.
10 Aux Auxiliary output
11 DI1 Configurable Digital Input 1
12 DI2 Configurable Digital Input 2
13 RS Remote Room Temperature Sensor
14 Scom Sensor Common
15 OS Outdoor Air (OA) Sensor
16 MS Not Used