User guide

46
Vertical Vent Termination
Appliance
Adapter
Firestop
Firestop/
Support
Roof
Flashing
Rain
Cap
Hanger
Strap
Elbow
Condensation
Drain (Install
According to
Local Codes)
3'
Max.
Terminate at least 6' from the
combustion air intake of any
appliance, and 3' from any
other building opening, gas
utility meter, service regulator
etc.
Enclose exterior vent systems
below the roof line to limit
condensation and protect
against mechanical failure.
When the vent penetrates a
floor or ceiling and is not
running in a fire rated shaft, a
firestop and support is required.
Terminate the vent system at
least 3' above, but not more
than 6' above the roof line, or
according to the vent pipe
manufacturer's instructions.
Provide vertical support every
12' or as required by the vent
pipe manufacturer's instructions.
Slope the horizontal vent 1/4"
downwards for every 12".
Do not vent straight upwards.
Always have a horizontal section
of venting.
Install a condensation drain in
the horizontal section of the
venting.