Instructions / Assembly
– 8 – 331552-002
600mm (24 in.) MIN.
FOR SERVICING
457mm
(18 in.)
MIN.
FLUE
SEE TABLE
TOP
SEE TABLE
FLUE
SIZES
SEE TABLE
NON-COMBUSTIBLE
FLOOR
COMBUSTIBLE
CEILING
DRAFT
REGULATOR
FLUE
SEE TABLE
NOTE: JW6 F307V requires additional
“Through-the-wall Vent Kit” available in
3 lengths:
5’ (63320),
10’ (63321) or
20’ (63322).
Refer to additional “Installation Instructions
for Through-the-wall Venting Components"
that is supplied with the JW6 F307V.
Model
Diam.
Flue location
Flue size
Clearance
Center Rear
Front Rear Sides Top Flue
mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.)
JW6 F307 508 (20) X
152 (6)
610 (24)
51 (2) 51 (2)
457 (18) 229 (9)
JW6 F507 559 (22) X
JW F657 660 (26) X 406 (16)
152 (6)
JW6 F307V 508 (20) X 457 (18)
152 (6) 152 (6) 356 (14) 457 (18)
178 (7)
JW717 813 (32) X
Figure 1. Installation Clearances