SECTION 8 - DIAGNOSTIC TROUBLE CODES
3121222 – JLG Lift – 8-19
996 POWER MODULE FAILURE -
INTERNAL ERROR
Drive, Steer, & Lift Prevented The System Module’s analog to digital converter does not
respond for the power PCB. This is an internal failure.
Cycle machine, if error still exists, replace System Module.
ZAPI - HEALTH (Status LED) - FLASHING
997 POWER MODULE FAILURE -
CHECK POWER CIRCUITS
OR MOSFET SHORT CIR-
CUIT
The power module detected an error in
the power wiring for the drive or pump.
Refer to Drive Motor Electrical Evaluation in Section 3.5.
Refer to Pump Motor Electrical Evaluation in Section 4.8.
Refer to Power Module Electrical Evaluation in Section 3.6.
998 EEPROM FAILURE - CHECK
ALL SETTINGS
The control system detected an
EEPROM failure.
•Replace ground board.
999 FUNCTION LOCKED OUT -
POWER MODULE SOFT-
WARE VERSION IMPROPER
The power module software version is not
compatible with the rest of the system.
Replace power module to clear fault.
9910 FUNCTION LOCKED OUT -
PLATFORM MODULE SOFT-
WARE VERSION IMPROPER
The platform board software version is
not compatible with the rest of the system.
Reprogram platform board.
9911 FUNCTION LOCKED OUT -
LSS MODULE SOFTWARE
VERSION IMPROPER
The load sensing system module soft-
ware version is not compatible with the
rest of the system.
Replace LSS module to clear fault.
9912 POWER MODULE FAILURE -
SYSTEM MONITOR
The ground board detected armature,
field, or pump current while function was
not commanded.
Refer to Drive Motor Electrical Evaluation in Section 3.5.
Refer to Pump Motor Electrical Evaluation in Section 4.8.
Refer to Power Module Electrical Evaluation in Section 3.6.
9924 FUNCTIONS LOCKED OUT -
MACHINE NOT CONFIG-
URED
The control system's memory indicates
that the vehicle has not been configured
(new control system components).
Use the JLG analyzer to adjust all machine setup and personality
settings, refer to 5.7 Machine Configuration Programming Infor-
mation.
9950 POWER MODULE FAILURE -
INTERNAL ERROR
Drive, Steer, & Lift Prevented The System Module’s armature power circuitry is driven without
PWM command for 100mS.
Cycle machine, if error still exists, replace System Module.
ZAPI - HEALTH (Status LED) - FLASHING
9951 POWER MODULE FAILURE -
INTERNAL ERROR
Drive, Steer, & Lift Prevented The System Module’s pump power circuitry is driven without
enable from the interface PCB for 100mS.
Cycle machine, if error still exists, replace System Module.
ZAPI - HEALTH (Status LED) - FLASHING
9952 POWER MODULE FAILURE -
INTERNAL ERROR
Drive, Steer, & Lift Prevented The System Module’s pump power circuitry is driven without
PWM command for 100mS.
Cycle machine, if error still exists, replace System Module.
ZAPI - HEALTH (Status LED) - FLASHING
9953 POWER MODULE FAILURE -
INTERNAL ERROR
Drive, Steer, & Lift Prevented The System Module’s field power circuitry is driven without
enable from the interface PCB for 100mS.
Cycle machine, if error still exists, replace System Module.
ZAPI - HEALTH (Status LED) - FLASHING
9954 POWER MODULE FAILURE -
INTERNAL ERROR
Drive, Steer, & Lift Prevented The System Module’s field power circuitry is driven without
reverse direction from the power PCB for 100mS.
Cycle machine, if error still exists, replace System Module.
ZAPI - HEALTH (Status LED) - FLASHING
9955 POWER MODULE FAILURE -
INTERNAL ERROR
Drive, Steer, & Lift Prevented The System Module’s field power circuitry is driven without for-
ward selection from the power PCB for 100mS.
Cycle machine, if error still exists, replace System Module.
ZAPI - HEALTH (Status LED) - FLASHING