Instructions / Assembly
NBseries Acidic Condensate pH Treatment Kits –– Installation/Operation & Maintenance
Inspect frequently
Installer — Instruct the building owner
to frequently inspect the NBT-23 tank
neutralizer and all condensate connec-
tions. The owner must notify a qualified
technician if any problems are noticed.
Recharge as required
When pH tank outlet falls below 5PH. Lo-
cal codes may have different requirement,
check with local authority.
At least at a minimum once a year.
Replacement parts
The ABS black baffle at the bottom of the
NBT-23 tank should be lifted out every
three years during re-charging for clean-
ing of the tank bottom. This should be
done by a trained technician.
Contact your local wholesaler or manu-
facturer’s representative for replacement
parts.
Dealer listing at www.jjmboilerworks.com
69 Ferry Street - Units 17 - 20
Easthampton, MA 01027 | 413-527-1893
2400 Feather Sound Drive, Clearwater, FL 33762
413-427-3373
jjmboilerworks.com
Revised - September, 2016
Maintenance
Wall Mounting Piping:
The NBT-23 can also be wall mounted by using the wall mounting brackets supplied with the unit. Always make sure that the method
of wall mounting will support the weight of a fully operating NBT-23 unit. (8.5 U.S. pounds). Piping and pipe clamps should also
be used.
Figure 8
A Boilers / Hot Water Heaters / Furnace Condensate Drains
B Flue Drain
C Single Flue Vent
D NBT-23 pH Treatment Tube Tank
E House Drain
F Boilers / Hot Water Heaters / Furnaces
G Condensate Trap
H Condensate Pump
Note: Contact Factory for pH Treatment Tank and Piping Size
C
F
B
A
E
Piping for Single Heating Unit/Individual NBT-23 pH Treatment Tank/
Condensate Pump & Common Flue Drain
H
G
Condensate Trap
Figure 8
Key
A
Rev. 01/2016
Flue Drain
B
C
D
E
F
Boilers/Hot Water Heaters/Furnaces Condensate Drains
Single Flue Vent
NBT-23 pH Treatment Tank
House Drain
Boilers, Hot Water Heaters, Furnaces
Note: Contact Factory for pH Treatment Tube and Tank Sizing and Piping Sizing
H
Condensate Pump
G
D
G
A Boilers / Hot Water Heaters / Furnace Common Drain
B Flue Drain
C Common Flue Vent
D NBT-23 pH Treatment Tank
E House Drain
F Boilers / Hot Water Heaters / Furnaces
G Condensate Trap
Note: Contact Factory for pH Treatment Tank Piping Size
7
Environmentally Friendly
The pH Power Pellets™ (Magnesium Hydroxide) pellets are NON-Hazardous to the
environment and can be disposed of as normal refuge. Do not allow children or ani-
mals to consume pH power pellets as they are not meant as a neutralizer for human or
animal consumption.
Important
Remove porous pellet bag from plastic shippig bag before placing in the NBT-23 tank.
MSDS and MDS sheets are included with the NBT-23 units or can be found on the JJM Boiler Works, Inc. website @ www.jjmboilerworks.com